Installation

Precautions Upon Installation

1. Select and install the CO

2

 concentration transmitter at a

location where it can detect typical concentrations of
CO

2

 in test gases and where the required air velocity

can be ensured.

2. Insert the CO

2

 concentration transmitter so that all of

the holes on the insert (bobbin) section are in the duct
(containing the test gas), and install so that the
direction of air flow matches the "

" on the cover.

3. We recommend using connectors for wiring to simplify

maintenance, inspection and calibration.

Installation

1. Prepare the exclusive mounting bracket.    Cut out a 30

mm dia. hole at the position where the CO

2

concentration transmitter is to be installed.

2. Fasten the mounting bracket and packing with the

screws provided.

3.

  Insert the bobbin into the bracket taking care to

insert it up to the topmost ventilation hole (hole closest
to the case).

  Tighten the bracket neck screws.

Lead Color

Item

White

24 VAC

Brown

24 VAC

Green

Output (-) common

Yellow

Output (+) 1 to 5 VDC

When a Separate Transformer Is Used

 CAUTION

Use an insulated transformer to supply 24
VAC power supply voltage.
Never share the 24 VAC power supply with
other equipment.
If a transformer is shared with other
equipment, a loop will be formed at common
and the transmitter may be damaged.

 

Transformer shared

Duct

Direction of
air flow

Tighten after
inserting
transmitter.

Insert

CO

concentration transmitter

Align arrow with direction
of air flow.

Packing

24V AC

Multi-loop

controller

CO

2

 concentration

transmitter

Y

CO

2

 concentration

transmitter

Shared

common

line

Common loop formed

×

NO GOOD