background image

 

 

8

 

AB-6464 

Actuator 

 CAUTION 

 

 

  Although the ACTIVAL can be used in high 

humidity environments (max. 95 % RH), do 
not immerse the actuator in water.     

  Although the ACTIVAL can be used out-

doors, be sure not to expose the actuator to 
direct sunlight. 

 
The ACTIVAL features a single unit construction with the 
actuator and valve combined together.    Do not separate. 
 

Position for shipment 

The actuator shaft is positioned at 100% (in fully open 
position) for shipment.    The shaft is completely turned 
counterclockwise, and the pointer points at “100”. (See 
Fig. 5) 

Figure 5.  Pointer position for shipment

 

 

Changing the Actuator Mounting Position 

1) Change the actuator mounting position only when the 

actuator is in fully open position. 

2) Remove the screws connecting the actuator and the 

yoke. Lift the actuator and detach it from the yoke. 
(Make sure that the groove at the top of the valve stem 
is parallel (in fully open position) to the piping.) <Step 
1 in Fig. 6> 

3) Remove the screws connecting the yoke and the valve 

body. <Step 2 in Fig. 6> 

4) Change the direction of the yoke to the desired 

direction.  The actuator can be horizontally rotated 
every 90

°

 to fit into the valve mounting position 

(0

°

/90

°

/180

°

/270

°

 from the factory preset position). 

<Step 3 in Fig. 6> 

5) A thermal insulation sheet is inserted between the 

yoke and the valve.  If the mounting position is 
changed, reinsert the thermal insulation sheet to fit 
into position (1 sheet between valve body and yoke). 

6) Before fixing the yoke to the valve with screws, check 

that the actuator engages correctly with the stem. 
(Check that the actuator pointer is in fully open 
position.) 

7) Mount the actuator, with its direction changed, to the 

yoke. <Step 4 in Fig. 6> 

 

IMPORTANT: 

Do not change the combination of valve body, 

yoke and actuator. 

 

 

 

Figure 6.    Changing the actuator mounting position 

 

 

 

Groove 

Valve stem 

Lift off acutator. 

Step 1 

Reposition acutuator and 

remount on yoke. 

Step 4 

Detach yoke from valve. 

Step 2 

Reposition yoke and 

remount on valve. 

Step 3 

2. 

3. 

4. 

1. 

Summary of Contents for ACTIVAL VY51XXJ

Page 1: ...n combination with a proportionally controlled electronic controller The nominal resistance 135 input provides proportional control in combination with a proportionally controlled electric controller...

Page 2: ...equipment damages Flush the piping so that no foreign substance remains Attach a strainer at upstream side of the piping to prevent equipment damages After the piping installation make sure no fluid...

Page 3: ...teel JIS SCS13A for large raised face RF type Plug and stem Stainless steel equivalent to JIS SCS Seat ring Heat resistant PTFE Gland packing Inorganic fiber Gasket Non asbestos joint sheet Piping con...

Page 4: ...Cover Plastic polycarbonate resin color gray Yoke Steel plate Surface finishing Case None Yoke Electro galvanizing bright chromate finish Installation locations Indoor Outdoor keep away from direct s...

Page 5: ...ctuator label and the wiring diagram label as follows Nominal 135 feedback potentiometer Nominal 135 resistance input 4 mA DC to 20 mA DC input 2 V DC to 10 V DC input Actuator valve Actuator Valve Ba...

Page 6: ...12 15 4 4 6 25 127 60 229 90 125 90 67 14 19 4 6 6 40 165 82 5 242 103 140 105 81 16 19 4 10 0 50 178 89 246 107 155 120 96 16 19 4 11 5 65 190 90 267 129 175 140 116 18 19 4 16 80 203 100 268 130 185...

Page 7: ...nspection Figs 1 and 2 show the minimum clearance for maintenance and inspection When installing the ACTIVAL in a ceiling space place a drain pan under the valve 3 Install a bypass pipe and gate valve...

Page 8: ...ully open position to the piping Step 1 in Fig 6 3 Remove the screws connecting the yoke and the valve body Step 2 in Fig 6 4 Change the direction of the yoke to the desired direction The actuator can...

Page 9: ...ing of 4 20 mA DC input and 2 10 V DC input refer to Figs 12 to 14 and make sure the polarity of power supply and 2 10 V DC output Incorrect wiring may result in PCB printed circuit board burnout To p...

Page 10: ...cted inside of the actuator Figure 13 Wiring terminal diagram Model VY514XJ00XX 2 10 V DC input with 2 10 V DC output type Note The terminals 2 5 and 7 are connected inside of the actuator Model VY511...

Page 11: ...esistance input B R T1 T2 Neostat Model TY900XZ Transformer Power supply W B R Connection with Model R35TC0 Model R36TC0 Power supply Model R35TC0 Model R36TC0 Model VY513XJ 4 20 mA DC input with 2 10...

Page 12: ...nnection of auxiliary switches OP1 OP2 OP3 OP4 OP5 OP6 Part No 83161792 001 Terminal block Auxiliary switch 1 Adjustable between 0 to 50 positions Auxiliary switch 2 Adjustable between 50 to 100 posit...

Page 13: ...e Misaligned piping Tighten the flange bolts Replace the gasket Redo piping Fluid leaks from the gland part Loosened gland packing Tighten the gland nut Fluid leaks from the bonnet Loosened bolts Tigh...

Page 14: ......

Page 15: ......

Page 16: ...Specifications are subject to change without notice Building Systems Company http www yamatake com Rev 2 0 Oct 2005 AB 6464 0 5H H W00 J AI 6464 Rev 1 0 Printed in Japan...

Reviews: