4
AB-6465
Actuator
Item Specification
Power supply
24 V AC ± 15 % 50 Hz/60 Hz
Applicable valve size
DN15 to DN80 of standard torque type
Power consumption
Nominal 135
Ω
feedback potentiometer type: 7 VA
Other types (nominal 135
Ω
resistance input, 4 mA DC to 20 mA DC input and 2 V DC to
10 V DC input): 8 VA
Timing 63
±
5 sec. (50 Hz) / 53
±
5 sec. (60 Hz)
Control signal
Nominal 135
Ω
feedback potentiometer
Feedback potentiometer
Total resistance: Nominal 135
Ω
Max. applied voltage: 5 V DC
Nominal 135
Ω
resistance input
4 mA DC to 20 mA DC input (input impedance: 100
Ω
)
2 V DC to 10 V DC input (input impedance: 150 k
Ω
or higher)
Analog output (only with 4 -20 mA DC
and 2-10 V DC inputs)
Range: 2 V DC (0 %) to 10 V DC (100 %)
Max. load: 10 k
Ω
or higher (Max. 1 mA)
Rated operating conditions
Transport storage conditions
-20
°
C to 50
°
C*
(Fluid temperature 0
°
C to 150
°
C)
Ambient
Temperature
-20
°
C to 40
°
C*
(Fluid temperature 150
°
C to 175
°
C)
-20
°
C to 70
°
C*
Humidity
5 %RH to 95 %RH
5 %RH to 95%RH
VIbration 4.9
m/s
2
(10 Hz to 150 Hz)
19.6 m/s
2
(10 Hz to 150 Hz)
Environmental conditions
(The actuator shall be packed during transport.)
∗
Note: Do not allow the fluid to freeze.
Materials
Case:
Aluminum alloy casting
Cover:
Plastic (polycarbonate resin) (color: gray)
Yoke: Steel
plate
Surface finishing
Case: None
Yoke: Electro-galvanizing (bright chromate finish)
Installation locations
Indoor
Outdoor (keep away from direct sunlight.)
Installation orientation
Installable in any position ranging from upright to sideways.
(If being installed outdoors, it must be installed in upright position.)
Valve position indication
Pointer located at the bottom of the actuator shows the position by pointing at the value of the
scale (0: close to 100: open) on front, rear, and bottom sides.
Manual operation
Discconect from the power supply. Using a wrench, rotate the rectangular part (joint) at the
connection between the valve and the actuator.
Refer to the section “Manually Opening/Closing Valve.”
Wiring
Two knockout holes (
φ
22 mm, for wiring port) are located on bilateral sides. Cut out the required
one and connect the wiring to the terminal block with screws (M3.5).
Enclosure rating
Splash-proof (equivalent to IEC (International Electrotechnical Commission) IP54)
Insulation
Between terminal and cabinet: 5 M
Ω
or higher at 500 V DC
Dielectric strength
Between terminal and cabinet: 500 V AC/min with 5 mA or less leakage current
Position for shipment
Fully open
Note:
For weight of the ACTIVAL, refer to the table shown in the section “Dimensions”.
50
40
30
-20
Ambient temperature (
°
C)
100 175
150
0
Fluid temperature (
°
C)