5-12
GENERATOR SYSTEM
ELEC
TROUBLESHOOTING CHART
WEAK OR NO DC CURRENT
No load engine speed inspection.
9
Operate the engine with no load.
2,600 r/min
GOOD
OUT OF SPECIFICATION
Check the throttle control system.
Refer to “THROTTLE CONTROL SYSTEM” in
CHAPTER 6.
Check the DC circuit breaker.
GOOD
DISCONNECTED
Replace the DC circuit breaker.
DC coil DC voltage inspection
9
Connect sub coil
2
White leads.
9
Start the engine, then measure the voltage. (Tester
range: DC 20V)
GOOD
TOO LOW
DOES NOT GENERATE
W
W
W
W
Or
Or L
L
2
DC coil DC voltage:
17 ~ 23 V at 20 °C (68 °F)
Replace the rectifier.
DC coil resistance inspection
9
Stop the engine.
9
Measure the resistance between the-White.
(Tester range:
Ω ×
1)
SPECIFICATION
OUT OF SPECIFICATION
W
W
W
W
2
DC coil resistance:
0.12
Ω
Ω
± 20% at 20 °C (68 °F)
Replace the DC coil.
Magnetic force is weak.
Replace the magneto rotor.