WIRING DIAGRAMS

Low Water Cut-Off Only

1. Main Line Switch - For burner circuits within the

switch’s electrical rating.

Pump Control Only

1. Install a starter or relay in pump control circuit,

as shown, to prevent damage to snap switch
and help insure proper switch/control operation.
Failure to do so may shorten the life of the
switch when actual amperage exceeds switch rating.

2. Connect wires from holding coil of pump starter

or relay to terminals 1 and 2 as shown.

NOTE:

To help insure most effective operation, 

balance boiler feed pump(s) to deliver required water
feed rate to match boiler steaming requirements.

1. Main Line Switch - For burner circuits within

the switch’s electrical rating.

2. Pilot Switch  - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

1 2

5 6

SEE PUMP

CONTROL

CIRCUIT

TO BURNER CONTROL CIRCUIT   

HOT

1 2

5 6

LOAD

LINE 

SEE PUMP

CONTROL

CIRCUIT

1 2

5 6

LOAD

LINE

1 2

5 6

LOAD

LINE

OR

OR

Combination Pump Control, Low Water Cut-Off and Alarm

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

8

LINE

LOAD

1 2

5 6

Summary of Contents for McDonnell & Miller 42S-N Series

Page 1: ...INSTRUCTION MANUAL MM 231G...

Page 2: ...ATER LINE PUMP OFF BURNER OFF BURNER CUT OFF LEVEL AT CAST LINE 1 3 8 35mm CUT OFF LEVEL NORMAL BOILER WATER LINE CUT OFF LEVEL PUMP OFF PUMP ON 3 4 19mm OPERATION Maximum Pressure 50 psi 3 5 kg cm2 E...

Page 3: ...Cut Off Pump Controller Must be Installed INSTALLATION TOOLS NEEDED Two 2 pipe wrenches one 1 flathead screw driver and pipe sealing compound IMPORTANT Follow the boiler manufacturer s instructions al...

Page 4: ...as depicted in the diagram to the bottom right OR If gauge glass tappings F and G are greater than 14 356 mm apart invert the black Y casting H as depicted in the diagram to the bottom right and inst...

Page 5: ...P Screw reducer bushing Q nipple R and blow off valve S into bottom 1 NPT tapping T Screw lower union tailpiece V with nut U into either 1 2 NPT lower tapping W X Screw 1 2 NPT pipe plug into unused...

Page 6: ...rient 1 2 NPT tapping FF with 1 2 tapping on control GG b Mount and pipe control HH on vertical equalizing pipes JJ at the required elevation as determined in Step 1 c Install gauge glass and other tr...

Page 7: ...h could result in property damage personal injury or death WARNING Switch Operation Boiler feed pump off burner on Boiler feed pump on burner on Boiler feed pump on burner off 1 2 5 6 1 2 5 6 1 2 5 6...

Page 8: ...n NOTE To help insure most effective operation balance boiler feed pump s to deliver required water feed rate to match boiler steaming requirements 1 Main Line Switch For burner circuits within the sw...

Page 9: ...ating ranges are shown on page 2 in the Operation section OFF ON If the burner comes on immediately turn the boiler off and make the necessary corrections Failure to follow this warning could cause an...

Page 10: ...urner is on slowly open the blow down valve NN until it is fully open Watch the gauge glass D to see that the water level drops Close the valve after verifying that the pump comes on and the burner sh...

Page 11: ...s on NOTE Refer to page 2 for switch operating points Open upper valve 1 Slowly open the lower valve 2 Water in the sight glass should lower As the water in the sight glass lowers the pump should turn...

Page 12: ...ngs and other wear parts or consumables all of which are not warranted except as otherwise provided in the quotation or sales form will be free from defects in material and workmanship for a period of...

Reviews: