• Connect wire “ a ” from power supply to 

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to 

t e rminal “ N ” .

• Connect wire “ c ” from pump control circuit

to terminal “ P N O ” .

• Connect wire “ d ” from pump control circuit

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control 

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit 

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm 

control circuit to terminal “ B C O M ” .

WIRING DIAGRAMS
Low Water Cut-Off, Alarm and Pump Up Control

• Connect wire “ a ” from power supply to 

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to 

t e rminal “ N ” .

• Connect wire “ c ” from pump #1 control 

circuit to terminal “ P N O ” .

• Connect wire “ d ” from pump #1 control 

circuit to terminal “ P C O M ” .

• Connect wire “ e ” from pump #2 control 

circuit to terminal “ B N C ” .

• Connect wire “ f” from pump #2 control 

circuit to terminal “ B C O M ” .

Dual Pump Control

• Connect wire “ a ” from power supply to 

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to 

t e rminal “ N ” .

• Connect wire “ c ” from va l ve control circuit 

to terminal “ P N O ” .

• Connect wire “ d ” from va l ve control circuit 

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control 

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit 

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm 

control circuit to terminal “ B C O M ” .

Motorized Valve and Low Water Cut-Off

FROM  BURNER OR ALARM

CONTROL CIRCUIT

TO  ALARM

CONTROL CIRCUIT

TO  BURNER

CONTROL CIRCUIT

FROM PUMP UP

CONTROL CIRCUIT

TO  PUMP UP

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

g

f

e

d

c

b

a

FROM PUMP #1

CONTROL CIRCUIT

FROM PUMP #2

CONTROL CIRCUIT

TO  PUMP #2

CONTROL CIRCUIT

TO  PUMP #1

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

f

e

d

c

b

a

FROM VALVE

CONTROL CIRCUIT

TO VALVE

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

d

c

b

a

FROM  BURNER OR ALARM

CONTROL CIRCUIT

TO  ALARM

CONTROL CIRCUIT

TO  BURNER

CONTROL CIRCUIT

g

f

e

Summary of Contents for McDonnell & Miller 1575 Series

Page 1: ...secondary redundant Low Water cut off controls be installed on all steam boilers with heat input greater than 400 000 BTU hour or operating above 15 psi of steam pressure At least two controls should...

Page 2: ...ctivated turning the pump on after water drops below the middle probe If the water level is not restored to the top probe within 3 m i nutes the pump relay will be deactivated shutting off the pump Af...

Page 3: ...System Water Temperature 406 F 208 C Maximum System Water Pressure 250 psi 17 6 kg cm2 Maximum System Steam Pressure 250 psi 17 6 kg cm2 All probes in the Series 1575 units are sent from the factory p...

Page 4: ...l water level but not lower than the lowest safe permissible water level as determined by the boiler manufacturer OR If the control will be the secondary low water fuel cut off size the steam top and...

Page 5: ......

Page 6: ...over Removal and Installation Procedure a To remove cover use a flathead screwdriver to loosen screws and remove the cover K b To reconnect cover slide over brackets and tighten screws using a flathea...

Page 7: ...p Control Connect wire a from power supply to terminal H Connect wire b from neutral supply to terminal N Connect wire c from valve control circuit to terminal PNO Connect wire d from valve control ci...

Page 8: ...PCB is too hot and the unit has shut down The unit will automatically restart when the PCB has cooled sufficiently When using the TEST button the green light will flash once per second during the time...

Page 9: ...nit is factory set at 0 seconds To adjust turn the adjusting screw clockwise using a small flatblade screwdriver to the delay time desired Followthe bl owdown procedure found on page 11 to verify oper...

Page 10: ...pect probes The wiring connections for the pump may not be connected properly Check wiring at terminals Burner does not turn off when water level is below longest probe The probes may be fouled with d...

Page 11: ...ld be opened slowly The piping needs to be wa rmed up and stagant water in the drain piping needs to be pushed out Suddenly opening a blow down valve causes steam to condense which may create water ha...

Page 12: ...poses Seller warrants the goods purchased hereunder with the exception of membranes seals gaskets elastomer materials coatings and other wear parts or consumables all of which are not warranted except...