6
en
– Original instructions
P26 Max RPM set
rpmx10
P27 Smin time
rpmx10
P28 Ramp 1
s
3
P29 Ramp 2
s
3
P30 Ramp 3
s
35
P31 Ramp 4
s
35
P32 Acceleration ramp at startup
s
2
P33 Deceleration ramp at shutdown
s
2
P34 Configuration of minimum speed
STP
P35 Minimum speed - Duration
s
0
P36 Adjustment window
%
10
P37 Hysteresis
%
80
P38 Speed Lift
rpmx10
P27
P39 Lift Amount
%
0
P41 Pressure Sensor Unit Of Measure
bar
P42 Full scale value for pressure Sensor 1 4÷20mA
bar/psi
16
P44 Zero Pressure Auto-Calibration
-
bar/psi
P45 Pressure Minimum Threshold
bar/psi
0
P46 Pressure Minimum Threshold - Delay Time
s
2
P47 Pressure Minimum Threshold
– Automatic Error Reset
ON
P48 Low water input
-
ERR
P50 Comm Protocol
-
MOD
P51 Communication protocol - Address
-
1
P52 Comm Protocol
– BAUDRATE
-
kbps
9.6
P53 BACnet Device ID Offset
-
002
P54 Communication protocol - Configuration
-
8N1
P55 Multipump
– Address
-
1
P56 Multipump
– Max Units
3
P57 Multipump
– Switch Interval
h
24
P58 Multipump
– Actual Value Increase
bar/psi
0.35
P59 Multipump
– Actual Value Decrease
bar/psi
0.15
P60 Multipump
– Enable Speed
rpmx10
P61 Multipump Synchronous
– Speed Limit
rpmx10
P62 Multipump Synchronous
– Window
rpmx10
150
P63 Multipump
– Priority
P64 Multipump
– Revision
P65 Test Run
– Time Start
h
100
P66 Test Run
– Speed
rpmx10
200
P67 Test Run
– Time Duration
s
10
P68 Default Values Reload
-
P69 Avoid Frequent Parameters Saving
-
NO
(
)
= Global parameter, shared by all pumps in the same multi-pump system
= Read only
- = Applicable to all units
Troubleshooting of alarms and errors
Code Description
Cause
Remedy
A03
Derating
Temperature too high
Lower the room temperature
Lower the water temperature
Lower the load
A05
Data memory alarm
Data memory corrupted
1. Reset the default parameters using parameter P68
2. Wait 10 s
3. Restart the pump
If the problem continues, contact Xylem or the Authorised
Distributor
A06
LOW alarm
Lack of water detection (if P48=
ALR)
Check the water level inside the tank
A15
EEPROM write failure Data memory damaged
Stop the pump for 5 minutes and then restart it again; if
the problem continues, contact Xylem or the Authorised
Distributor
A20
Internal alarm