19
9.
TOTAL RUN TIME
0000:00
Runtime of the motor.
This time can be reset together with the
Operating hours.
Press the
¾
button to change to
Note: All changes have to be saved, that they will not be lost in case of shut off
of the power supply !!
10.
SAVE ???
Ï
+
Ð
Simultaneously press buttons
Ï
and
Ð
until...:
11.
SAVE ???
SAVED
appears on the display. After five seconds the
display jumps back to the 1
st
display.
These parameters can also be set during operation; To do so, briefly press the button
¾
and repeat steps 1 – 10.
Note: Often shown displays:
12.
INVERTER LOCKED
enable inverter
This message appears when the connection of
terminal X1/4-X1/5 is open (external release contact).
To start the Hydrovar-Smart, connect these terminals by closing the external release contact
or by using a short-circuit connection!