High Temp Sump Pump

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTRUCTION MANUAL

IM248R03

Summary of Contents for GOULDS WEHT0311M

Page 1: ...High Temp Sump Pump INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS INSTRUCTION MANUAL IM248R03 ...

Page 2: ...UBJECT PAGE Introduction 3 Safety Instructions 3 Performance and Motor Details 3 Pre Installation Checks 3 Lifting of Pump 4 Optional Guide Rail or Lift Out System 4 Piping 4 Wiring and Grounding 4 Selecting and Wiring Pump Control Panels and Switches 4 Installation 5 Operation 5 Float Switch and Panel Chart 6 Insulation Resistance Readings 7 Engineering Data 7 Troubleshooting 8 Typical Installati...

Page 3: ...nal injury or equip ment damage Failure to follow manufacturer s installa DANGER WARNING CAUTION tion instructions may result in electrical shock fire hazard personal injury or death damaged equipment provide unsatisfactory performance and may void manufacturer s warranty Standard units are not designed for use in swimming pools open bodies of water hazardous liquids or where flammable gases exist...

Page 4: ... valve matched to the solids handling capability of the pump to prevent fluid backflow Backflow can allow the pump to turbine backwards and may cause premature seal and or bear ing wear If the pump is turning backwards when it is called on to start the increased torque may cause dam age to the pump motor and or motor shaft and some single phase pumps may actually run backwards Install an adequatel...

Page 5: ...AND WIRING PUMP CONTROL PANELS AND SWITCHES FLOAT SWITCH TYPES High Temp floats can be purchased for High Temp ap plications They are normally open NO for pump down operations These wide angle pump down switches may be used as direct connected pump switches or as control switches SETTING THE FLOAT SWITCHES There are no absolute rules for where to set the float switches it varies from job to job Su...

Page 6: ...t place pump switch es in the Au tomatic position and Control Switch in ON position The system is now ready for automatic operation Explain the operation of the pumps controls and alarms to the end user Leave the paperwork with the owner or at the control panel if in a dry secure location FLOAT SWITCH AND PANEL CHART The purpose of this chart is to show the required switch quantities and the funct...

Page 7: ... are based on readings taken with a megohmmeter with a 500V DC output Readings may vary using a lower voltage ohmmeter consult factory if readings are in question ENGINEERING DATA PUMP OPERATION Figure 2 Determining Pumping Range Figure 1 Pumpmaster and Pumpmaster Plus Hard Wired Engineering data for specific models may be found in your catalog and on our website address is on the cover Control pa...

Page 8: ...velcordstangled Untanglecordsandinsurefreeoperation TURNOFF Pumpisairlocked Shutoff pumpforapproximatelyoneminute then restart Repeatuntilairlockclears If airlocking persistsinasystemwithacheckvalve a3 16 4 8mm holemaybedrilledinthedischargepipeapproximately 2 51mm abovethedischargeconnection Influentflowismatchingpump s Largerpumpmayberequired dischargecapacity LITTLEORNOLIQUID Checkvalveinstalle...

Page 9: ...9 TYPICAL INSTALLATIONS Typical Effluent Sewage and Dewatering Pump Installations ...

Page 10: ...10 NOTES ...

Page 11: ...11 NOTES ...

Page 12: ...oper electrical protection or g damaged resulting from the use of accessory equipment not sold or approved by Seller In any case of products not manufactured by Seller there is no warranty from Seller however Seller will extend to Buyer any warranty received from Seller s supplier of such products Goulds Water Technology Policy Concerning Online Sales to Consumers Homeowners using the Internet to ...