Control cables
External volt free contacts must be suitable for switching < 10 VDC.
NOTICE:
• Install the control cables separate from the power supply cables and the fault signal
relay cable
• If the control cables are installed in parallel with the power supply cable or the fault
signal relay, the distance between the cables must exceed 200 mm
Do not intersect the power supply cables; should this be necessary, a 90° intersection
angle is permitted.
Table 4: Recommended control cables
Smart motor control cables
Wires number x Max.
copper Section
AWG
Tightening torque
All I/O conductors
0.00012-0.0023 sq.in
0.75-1.5 mm
2
18-16 AWG
5.4 lb-in
0.6 Nm
4.3.3 Power supply connection
Electrical Hazard:
Contact with electric components may cause death, even after the unit has been switched
off. Before any interventions on the unit, the network voltage and any other input voltages
must be disconnected for the minimum time indicated in Table 9 (Wait times).
Table 5: Power supply wiring procedure
Reference
1. Open the terminal box cover (2) by removing the
screws (1).
2. Insert the power cable in the M20 cable gland (5)
Fig. 9
1. Connect the cable according to the wiring diagram.
2. Connect the earth conductor (mass), making sure
that it is longer than the phase conductors.
3. Connect the phase leads.
Fig. 14
1. Close the cover (2) and tighten the screws (1).
Fig. 9
Table 6: I/O wiring procedure
Reference
1. Open the terminal box cover (2) by removing the
screws (1).
Fig. 9
1. Connect the cable according to the wiring diagram.
Fig. 15
1. Close the cover (2) and tighten the screws (1).
Fig. 9