Shield Termination (Cable Screen)

The safety ground terminal provides a grounding point for the motor cable shield. The
motor cable shield connected to this terminal (drive end) should also be connected to the
motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to
the safety ground terminal.

Wiring Precautions

Connect the SRC 311 according to 

Drive and Motor Connection

 (page 12) and 

Motor

Terminal Box Connections

 (page 12), ensuring that motor terminal box connections are

correct. There are two connections in general: Star and Delta. It is essential to ensure that
the motor is connected in accordance with the voltage at which it will be operated. For
more information, refer to 

Motor Terminal Box Connections

 (page 12).

It is recommended that the power cabling should be 4-core PVC-insulated screened cable,
laid in accordance with local industrial regulations and codes of practice.

Incoming Power Connection

• For a single phase supply, power should be connected to L1/L, L2/N.
• For 3 phase supplies power should be connected to L1, L2, and L3. Phase sequence is

not important.

• For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is

recommended.

• A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting

device installed between the SRC 311 and the AC Power Source. The disconnecting
device must conform to the local safety code / regulations (e.g. within Europe,
EN60204-1, Safety of machinery).

• The cables should be dimensioned according to any local codes or regulations.

Guideline dimensions are given in 

Output power and current ratings

 (page 18).

• Suitable fuses to provide wiring protection of the input power cable should be

installed in the incoming supply line, according to the data in 

Output power and

current ratings

 (page 18). The fuses must comply with any local codes or regulations

in place. In general, type gG (IEC 60269) or UL type T fuses are suitable; however in
some cases type aR fuses may be required. The operating time of the fuses must be
below 0.5 seconds.

• Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers

of equivalent rating may be utilized in place of fuses, providing that the clearing
capacity is sufficient for the installation.

• When the power supply is removed from the drive, a minimum of 30 seconds should

be allowed before re-applying the power. A minimum of 10 minutes should be
allowed before removing the terminal covers or connection.

• The maximum permissible short circuit current at the SRC 311 Power terminals as

defined in IEC60439-1 is 100kA.

• An optional Input Choke is recommended to be installed in the supply line for drives

where any of the following conditions occur:
• The incoming supply impedance is low or the fault level / short circuit current is high
• The supply is prone to dips or brown outs
• An imbalance exists on the supply (3 phase drives)
• The power supply to the drive is via a busbar and brush gear system (typically

overhead Cranes).

• In all other installations, an input choke is recommended to ensure protection of the

drive against power supply faults.

• SRC 311 models in frame sizes 4 to 6 are factory fitted with an Input choke as standard.

Installation

SRC 311 - SmartRun

 User guide

11

Summary of Contents for FLYGT SmartRun SRC 311

Page 1: ...SRC 311 SmartRun User guide ...

Page 2: ......

Page 3: ...er 9 Electrical Installation 10 Grounding the Drive 10 Wiring Precautions 11 Incoming Power Connection 11 Drive and Motor Connection 12 Motor Terminal Box Connections 12 Control Terminal Wiring 12 System Description 15 Display and buttons 15 Communication 15 Technical Reference 17 Facility requirements 17 Input voltage 17 Maximum supply ratings for UL compliance 18 Output power and current ratings...

Page 4: ...ctions see Installation Operation and Maintenance manual 5 Motor cable Sizes see Output power and current ratings page 18 6 Motor connections check for Star or Delta connection according to the motor voltage rating Motor Nameplate Details Motor rated voltage Motor rated current Motor rated frequency Motor rated speed Optional 7 AC Supply Connection see Output power and current ratings page 18 200 ...

Page 5: ...When using an SRC 311 with an internal or optional external filter compliance with the following EMC Categories as defined by EN61800 3 2004 can be achieved Drive Type Rating EMC Category Cat C1 Cat C2 Cat C3 1 Phase 230 Volt Input SRC311 X 2 XXXXX XX No additional filtering required Use screened motor cable 3 Phase 400 Volt Input SRC311 X 4 XXXXX XX Use External Filter No additional filtering req...

Page 6: ...nmental limitations Do not perform any flash test or voltage withstand test on the SRC 311 Any electrical measurements required should be carried out with the SRC 311 disconnected Electric shock hazard Disconnect and ISOLATE the SRC 311 before attempting any work on it High voltages are present at the terminals and within the drive for up to 10 minutes after disconnection of the electrical supply ...

Page 7: ...ufacturers of the motor and the driven machine about suitability for operation over the intended speed range prior to machine start up Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation The SRC 311 has an Ingress Protection rating of IP55 and are intended for indoor use only When mounting the drive ensure that sufficient cooli...

Page 8: ... to Environment Before Installation Carefully Unpack the SRC 311 and check for any signs of damage Notify the shipper immediately if any exist Check the drive rating label to ensure that it is of the correct type and power requirements for the application Store the SRC 311 in its box until required Storage must be clean and dry and within the temperature range 40 C to 60 C UL Compliant Installatio...

Page 9: ...0 0 21 26 865 0 34 06 B mm in 418 0 16 46 515 0 20 28 830 0 32 68 C mm in 423 0 16 65 520 0 20 47 840 0 33 07 D mm in 8 0 0 315 8 0 0 315 10 0 0 394 E mm in 230 0 9 06 270 0 10 63 340 0 13 39 F mm in 173 0 6 81 235 0 9 25 290 0 11 42 G mm in 110 0 4 33 175 0 6 89 200 0 7 87 H mm in 4 25 0 167 4 25 0 167 5 50 0 217 I mm in 7 5 0 295 7 5 0 295 11 0 0 295 Torque values for installation Screw Frame si...

Page 10: ...5 2 5 4 5 22 5 39 8 6 8 70 8 Mounting clearance Y X X Y X Minimum 200 mm 7 87 in Y Minimum 10 mm 0 349 in Typical drive heat losses are 3 of operating load conditions NOTICE The operating ambient temperature of the drive must be maintained Installation 8 SRC 311 SmartRun User guide ...

Page 11: ...g a suitable flat blade screwdriver rotate the four retaining screws indicated until the screw slot is vertical Terminal Cover Release Screws Frame Size 6 Remove the two screws indicated lift the cover forwards and off To refit the cover slide the top locating lugs upwards under the top cover then re fasten the lower cover screws Installation SRC 311 SmartRun User guide 9 ...

Page 12: ...oop impedance must confirm to local industrial safety regulations To meet UL regulations UL approved ring crimp terminals should be used for all ground wiring connections The drive Safety Ground must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connections shou...

Page 13: ...local codes or regulations Guideline dimensions are given in Output power and current ratings page 18 Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line according to the data in Output power and current ratings page 18 The fuses must comply with any local codes or regulations in place In general type gG IEC 60269 or UL type T fuses ...

Page 14: ...cable screen should be terminated at the motor end using an EMC type gland allowing connection to the motor body through the largest possible surface area Where drives are mounted in a steel control panel enclosure the cable screen may be terminated directly to the control panel using a suitable EMC clamp or gland as close to the drive as possible For IP55 drives connect the motor cable screen to ...

Page 15: ...reen 14 Level switch 15 Gray lead EU Red lead US 16 Screen of the shared communication cable 17 Signal leads of the shared communication cable 18 Pump 2 19 T1 pump 2 20 T2 pump 2 21 T31 pump 1 22 T41 pump 1 23 Screen of the shared communication cable 24 Screen of the level sensor cable 25 Level sensor 26 Blue lead 27 Red lead 28 White Figure 1 Electrical connection drawing Table 1 Power Terminal T...

Page 16: ...sed 6 Analog input 0 20 mA Pump sensor T2 7 Ground 8 Analog output 4 20 mA Level sensor output 9 Ground earth 10 Analog input 4 20 mA Level sensor input 11 Digital output 0 10 V Pump running output 12 Hardware inhibit input 13 Hardware inhibit output 0 V Relay 14 Relay 1 common Sum alarm relay contact 250V AC 30V DC 5A 15 Relay 1 NO Sum alarm relay contact 250V AC 30V DC 5A 16 Relay 1 NC Sum alarm...

Page 17: ...ed to turn off the drive Down key is used to decrease a value or selection in the submenu Hand key is used to enter the manual mode Auto key is used to enter the automatic mode Communication SRC 311 is equipped with an RJ45 connector The connection is used to set up a network via a wired connection The connector contains two independent RS485 connections and both can be used simultaneously System ...

Page 18: ...ote key pad 7 RS485 Modbus RTU CanOpen 8 RS485 Modbus RTU CanOpen All SRC 311 parameters are read and set over the fieldbus communication Process parameters marked as setting is also accessed and read but process parameters marked as fixed value cannot be read or set over the fieldbus communication Any external system that wants to read process data and alarms from SRC 311 must be configured with ...

Page 19: ...2 5 per 1 C 1 8 F for IP66 Maximum 50 122 Storage 40 60 40 140 Humidity requirements The relative humidity must not exceed 95 non condensing Air requirements The air surrounding the unit must be free from Excessive dust Acids Corrosive gas Salt Input voltage Depending upon the model and power rating the drives are designed for direct connection to the following supplies Model Number Supply Voltage...

Page 20: ...mm2 Nominal Output Current A 150 Output Current 60 seconds A SUBCAB cable mm2 4 0 5 0 3 17 3 32 6 0 18 0 19 80 2 5 Table 5 380 480 V 10 3 phase input 3 phase output kW HP Frame Size Nominal Input Current A Fuse MCB type B A Supply cable mm2 Nominal Output Current A 150 Output Current 60 seconds A SUBCAB cable mm2 4 0 5 0 2 10 8 16 2 5 9 5 10 45 1 5 5 5 7 5 3 13 3 20 2 5 14 0 15 40 2 5 7 5 10 0 3 1...

Page 21: ... 00 25 0 75 0 120 6 150 2 160 70 0 150 0 165 00 35 0 Cable length The maximum cable length is 100 m 328 ft Screened cables must be used The PWM output switching from any inverter using a long motor cable can cause an increase in the voltage at the motor terminals depending on the cable length and inductance The rise time and peak voltage can affect the service life of the motor Flygt recommends us...

Page 22: ......

Page 23: ......

Page 24: ...buildings factories and farms In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise backed by a legacy of innovation For more information on how Xylem can help you go to xyleminc com Xylem Water Solution AB Gesällvägen 33 174 87 Sundbyberg Sweden Tel 46 8 475 60 00 Fax 46 8 ...

Reviews: