3. Change to the correct date and time.
4. Select and click the check mark to confirm the new settings.
8.4.5 Enable or disable a function
Most of the functions are enabled by default.
1. Go to Settings > Pump Control.
2. Select the function.
3. Select one of the following steps:
Condition
Action
The function is enabled.
Clear the check box to disable the function.
The function is disabled.
Select the check box to enable the function.
8.4.6 Configure the Minimize Fat Build-Up function
The function is not enabled by default.
1. Go to Settings > Pump Control > Minimize Fat Build-Up.
2. Enable the function.
3. Open Maximum Random Level or Maximum Random Delay.
4. Configure the parameter.
The setting is in meters or feet for an analog sensor and in seconds for a float
switch.
8.4.7 Modify the alarm settings
1. Go to Settings > Alarms.
2. Select the alarm.
3. Select and configure the parameters:
Parameter
Action
Activation Delay
Select and change the parameter.
Deactivation Delay
Select and change the parameter.
Control Lamp
Default: Enabled
Control Relay
Default: Enabled
8.4.8 Configure the Motor Protection function
In the wizard, the settings for current limits and sensor type are set to the same
value for both the pumps in a two-pump station. If the pumps are different, the
settings have to be changed.
1. Go to Settings > Motor Protection.
2. Select and configure the following parameters for each pump.
– Full Load Current
– Overcurrent Threshold
– Sensor Type
8 System Setup and Operation
32
Flygt FGC 400 Installation, Operation, and Maintenance