8.2 Commissioning
For more information about the menus, see
(page 39).
Power on the controller.
Condition
Action
First start of the controller without USB
drive.
1. Select Setup Wizard.
2. Proceed with
(page
29).
First start of the controller with USB drive. Select Restore from USB and follow the instructions.
Start of controller with existing
configuration
The Home menu appears.
The setup wizard is always accessible.
8.3 Run the setup wizard
1. Start through the wizard.
Use the jog wheel to select and confirm.
Menu
Action
Language
Select the language.
Unit of Measurement Select metric or imperial system. This option appears only when the English
language has been selected.
Date/Time Settings
Navigate, select, and change to the correct date and time. Confirm the
settings.
Number of Pumps
Select number of pumps.
2. Select and configure the level sensor.
Option
Action
Analog
Select and configure:
1. Sensor Range
2. Duty Start Level
3. Standby Start Level
4. Pump Stop Level
Open Bell
Select and configure:
1. Duty Start Level
2. Standby Start Level
Float Switches
Go to the next menu.
3. Continue through the wizard.
8 System Setup and Operation
Flygt FGC 400 Installation, Operation, and Maintenance
29