External Hand-Off-Auto control
Hand on: DI3 is high and DI4 is low
Hand off: DI3 is low and DI4 is high
Auto: DI3 is low and DI4 is low
Pump run feedback
DO1
Sum alarm A
DO2
Sum alarm B
DO3
Pump cleaning in progress
DO4
Actual power
AO 4–20 mA
4 mA = Minimum power
20 mA = Set power
5. Connect the power cables.
6.3.4.2 Connect the cables, FPG 412
For more information about the connection terminals, see
on page 49.
1. Connect T3 and T4 from the pump.
2. Connect the drain wire to functional ground (earth).
3. Connect the HMI.
4. Connect the external control system.
For more information about connections with Modbus, see separate documentation.
Cable
Terminal
Pump run
DI1
DI1 is high: Pump active
DI1 is low: Pump inactive
Reference power
AI 4–20 mA
4 mA = Minimum power
20 mA = Set power
Alarm reset
DI2
External Hand-Off-Auto control
Hand on: DI3 is high and DI4 is low
Hand off: DI3 is low and DI4 is high
Auto: DI3 is low and DI4 is low
Pump run feedback
DO1
Sum alarm A
DO2
Sum alarm B
DO3
Pump cleaning in progress
DO4
Actual power
AO 4–20 mA
4 mA = Minimum power
20 mA = Set power
5. Connect the power cables.
6.3.4.3 Set the switches
Set the switches.
Switch
Correct setting
NODE ADDRESS, 0 – 9
All the node addresses on the same backplane bus must be unique and not 0.
TERM, ON/OFF
The last unit in a Modbus network must be set to ON.
MASTER/SLAVE
FPG 411, FPG 412: SLAVE