CentriPro
P
C
PL
U
S
Automatic Pump Controller
Installation, Operation and
Maintenance Manual
TABLE OF CONTENTS
Specifications ...................................................................................... 2
Safety Precautions .............................................................................. 3
Installation ........................................................................................... 4
Wiring Diagram .................................................................................. 4
Assembly Instructions ....................................................................... 6
Electrical Connection ........................................................................ 7
Unit Starting and Working ............................................................... 8
Trouble Shooting Guide ................................................................... 9
PC
PLUS
Dimensional Drawing .................
.....
................................
10
CentriPro Limited Warranty ........................................................... 12
CONGRATULATIONS!
You are now a proud owner of a quality CentriPro product. For best results,
please read this Installation, Operation and Maintenance (IOM) carefully before
installing and using this product.
SAFETY PRECAUTIONS
This symbol
together with one of the following words “Danger” or
“Warning” indicates the risk level deriving from failure to observe the prescribed
safety precautions:
DANGER:
Risk of electrical shock. Warns that failure to
observe the precautions involves a risk of electric shock.
DANGER:
Warns that failure to observe the precautions
involves a risk of damage to persons and / or things.
WARNING:
Warns that failure to observe the
precautions involves a risk of damaging the product.
SPECIFICATIONS
Input voltage
220- 240 V
Frequency
50/60 Hz
Maximum working pressure
PC
PLUS
12
Bar
Maximum working temperature
6
5
°C
Maximum Current
PC
PLUS
10
A
Connection
1” male
Protection rating
IP65
Pre-set Pressure
PC
PLUS
1.5 to
2.
2
Bar
Make sure that the mains voltage corresponds to the voltage specified
on the faceplate and the reference characteristics (frequency, and
input current) are shown in this IOM.
The connections to the mains and grounding must be executed by
qualified personnel and in compliance with local installation standards.
Open the terminal (front) box lid and carry out connections as per the
diagram on it.
Pay attention to the working limits. Improper use may damage the
controller and other property, and injure people.
Make sure that the rated voltage and the mains voltage are
compatible.
Connect to the power mains using a multi-pole power with a switch-
contact gap of at least 3 mm. As additional protection from lethal
electric shock, install a high-sensitivity differential “RCD/Earth-
Leakage” switch.
Make sure unauthorised people do not have access to the unit.
Disconnect the power supply to the unit or unplug the machine before
carrying out any maintenance, cleaning or handling operations. If the
power cord is damaged it must be replaced by qualified personnel to
ensure against hazards.
Be alert to hazardous situations caused by accidental power failure.
Make sure the unit is properly ventilated. Warning: the motor can reach a
temperature of 95°C.