2

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL INJURY  

OR MAJOR PROPERTY DAMAGE, READ AND 

FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL 

AND ON EQUIPMENT.
THIS MANUAL IS INTENDED TO ASSIST IN THE 

INSTALLATION AND OPERATION OF THIS UNIT  

AND MUST BE KEPT WITH THE UNIT.

This is a 

SAFETY ALERT SYMBOL

.  

When you see this symbol on the 

pump, the controller or in the manual, 

look for one of the following signal 

words and be alert to the potential for 

personal injury or property damage.
Warns of hazards that 

WILL

 cause 

serious personal injury, death or major 

property damage.
Warns of hazards that 

CAN

 cause 

serious personal injury, death or major 

property damage.
Warns of hazards that 

CAN

 cause  

personal injury or property damage.

NOTICE:  

INDICATES SPECIAL    

 

 

INSTRUCTIONS WHICH ARE    

 

VERY IMPORTANT AND MUST BE  

 FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS   AND 

WARNINGS PRIOR TO PERFORMING ANY WORK 

ON THIS CONTROLLER.
MAINTAIN ALL SAFETY DECALS.

DANGER

WARNING

CAUTION

Disconnect and lockout electrical power 
before installing or servicing any  

electrical equipment.

ELECTROCUTION HAZARD. 

CONTROLLER INPUT GROUND 

TERMINAL (GND) AND ALL EXPOSED METAL 

PIPING, INCLUDING PRESSURE TRANSDUCER 

CASE, MUST BE CONNECTED TO THE SERVICE 

ENTRANCE GROUND TERMINAL.

All electrical work must be performed 

by a qualified technician. Always follow 

the National Electrical Code (NEC), or the Canadian 
Electrical Code, as well as all local, state and provincial 
codes. Code questions should be directed to your 
local electrical inspector. Failure to follow electrical 
codes and OSHA safety standards may result in 
personal injury or equipment damage. Failure to 
follow manufacturer’s installation instructions may 

result in electrical shock, fire hazard, personal injury 

or death, damaged equipment, unsatisfactory 
performance, and may void manufacturer’s warranty.

WARNING

WARNING

WARNING

5VDC MOISTURE SENSOR RELAY

INSTALLATION INSTRUCTIONS

The Sensor can detect the presence of water and 

provide a relay output for signal or control of an 

external device. The switch operates on voltage DC 

and functions as a Normally Closed Sensor, for a 

Closed Loop system. The Red and Black wires power 

the switch while the White and Green wires are the 

relay output wires.

SPECIFICATIONS

Power Requirements: 

9K585 9K584 9K583

Operating Voltage 

5 Volts DC 

12 Volts DC 

24 Volts DC

Operating Current 

10 mA 

10 mA 

10 mA

Contact Characteristics:

Contact Resistance 

100 m

Ω 

100 m

Ω 

100 m

Ω

Switching Voltage 

30 Volts DC Max 

30 Volts DC Max 

30 Volts DC Max

Switching Current 

500 mA Max 

500 mA Max 

500 mA Max

Power 

250 mW Max 

250 mW Max 

250 mW Max

Wire Connections:

Red 

5 Volts DC 

12 Volts DC 

24 Volts DC

Black 

- Ground 

- Ground 

- Ground

Green 

Relay Contact 

Relay Contact 

Relay Contact

White 

Relay Contact 

Relay Contact 

Relay Contact

For installation to an alarm panel, the Red wire is 

connected to the positive side of a voltage supply 

and the Black wire is connected to the negative. 

The Green and White wires can then be connected 

to any pre-selected Closed Loop zone. A resistor 

can be connected in series with either the Green or 

White wire for those panels that require end-of-line 

resistance.
After installation these units should be tested with a 

damp sponge or paper towel and inspected annually. 

If there is any corrosion or damage the sensor should 

be replaced.

Summary of Contents for CentriPro 9K585

Page 1: ...nd SOLO2 Connections to S Drive and SPD Connections to Aquavar AB2 AquaBoost II Connections to e SM Smart Motor Connections to Aquavar IPC Connections to Hydrovar INSTALLATION AND OPERATION MANUAL FOR...

Page 2: ...ty standards may result in personal injury or equipment damage Failure to follow manufacturer s installation instructions may result in electrical shock fire hazard personal injury or death damaged eq...

Page 3: ...arked R on controller WIRING 2 OR MORE MOISTURE SENSOR RELAY IN SERIES Connect Black and Red wires to the transducer terminal Connect the white wire from sensor 1 and green wire from sensor 2 to the R...

Page 4: ...nsor to terminal marked Input Wht on controller Connect White wire from Moisture Sensor to the White wire of the pressure transducer cable with a wire nut S DRIVE AND AQUAVAR SPD Connect White and Gre...

Page 5: ...eSM Smart Motors Connect green wire from Moisture Sensor to terminal 11 Start on eSM Connect red wire from Moisture Sensor to terminal 6 15VDC on eSM Connect white wire from Moisture Sensor to termina...

Page 6: ...sor Part Number 9K583 to IPC and Hydrovar Connect red and green wires from Moisture Sensor to terminal 13 24 V OUT on IPC Connect white wire from Moisture Sensor to terminal 18 D IN on IPC Connect bla...

Page 7: ...oisture Sensor to terminal 18 ON OFF on Hydrovar Connect red wire from Moisture Sensor to terminal 4 24V on Hydrovar Connect black wire from Moisture Sensor to terminal 6 GND on Hydrovar Connect white...

Page 8: ...d Street Ext Suite A Seneca Falls NY 13148 Tel 866 673 0445 Fax 888 322 5877 www xylem com centripro CentriPro and Aquavar Solo are trademarks of Xylem Inc or one of its subsidiaries 2021 Xylem Inc IM...

Reviews: