background image

en – Original Instructions 

 

 

Installation, Operation and Maintenance Manual 

31

 

 

5.4

 

Air purge 

After filling the system with liquid, any residual air shall be removed from the pump housing. To 

aid this effort, the standard  pump

 

models with control  knob are equipped with a built-in air 

purge function.  

For activation, turn the knob to the right end position for 5 seconds (the air purge symbol is 

shown  on the scale, see Figure  15).  A 10 minute long air purging sequence starts, which 

includes several max and min speed sequences, stoppages. It is indicated with the knob flashing 

green. You may set the knob to the desired speed level during the air purge sequence. After 

the sequence is finished, the pump will continue to operate in the preset speed level. 

You can interrupt the air purge sequence via turning the knob under its halfway position and 

turning it back to the end position again. Or simply switch off and then on the mains power. 

Audible flow noises indicate if there is still air in the pump. In this case repeat the air purging. 

 

Figure 15

 

5.5

 

Setting the timer 

To increase the overall efficiency of a hot water recirculating system, some pump models are 

equipped with a plug-in timer unit (it is also available as an installation kit for retrofitting; for 

ordering, contact your local distributor). The timer control is programmable to turn the circulator 

on and off automatically at preset times. This allows domestic hot water to be circulated only at 

the expected times of high usage. 

 

 

NOTICE: 

The timer mechanism allows turning the setting dial only in clockwise direction (as indicated by 

the arrows as well). Do not force it counterclockwise, it may damage the unit. 

Timer programming 

1.

 

Using a small flat-head screwdriver, pry the 

timer cover open and fold it under the unit.

 

 

2.

 

Set the current time by turning the setting 

dial in the direction of the arrows, until the 

actual time is aligned with the pointer 

above the dial face.

 

The illustration shows the correct setting in 

case the actual time is 6 a.m. 

The scaling is for a whole 24 hours in a 

graduation of 30 minutes. 

The ratchet mechanism allows turning the 

dial only in clockwise direction, do not 

force it counterclockwise. One “click” 

represents approx. 5 minutes.

 

 

Summary of Contents for Bell & Gossett Autocirc e3-4 Series

Page 1: ...Installation Operation and Maintenance Manual Series e3 4 e3 6 Instant hot water recirculating systems...

Page 2: ...n 11 3 2 Integrated features and functions 11 3 3 Data plate 12 3 4 Model description 12 3 5 Names of the main components and accessories 13 3 6 Intended use 14 3 7 Improper use 16 4 Installation 17 4...

Page 3: ...Maintenance 36 6 1 Precautions 36 6 2 Maintenance 36 6 3 Autocirc pumps 37 6 4 Disassembly 37 7 Troubleshooting 38 7 1 Precautions 38 7 2 Error signals 38 7 3 Pump not running 38 7 4 Pump running for...

Page 4: ...documentation Special version pumps may be supplied with supplementary instruction manuals For situations not considered in the manual or in the sales document contact Xylem or the Authorized Distribu...

Page 5: ...ntifies a dangerous situation which if not avoided may cause small or medium level injuries NOTICE It identifies a situation which if not avoided may cause damage to property but not to people Complem...

Page 6: ...t according to NSF ANSI 61 SAFETY INSTRUCTIONS according to UL 778 CAUTION Acceptable for indoor use only This pump has been evaluated for use with water only Use with maximum 203 F 95 C water WARNING...

Page 7: ...pump and have the problem corrected by a qualified service representative before using NSF ANSI 61 limitation CAUTION Do not allow the temperature above 140 F 60 C in systems circulating drinking wat...

Page 8: ...components to cool before you handle them Make sure that the product has been thoroughly cleaned Disconnect and lock out power before you service the pump Precautions during work Observe these safety...

Page 9: ...n on the transport document In both cases promptly contact Xylem or the Authorized Distributor from whom the product was purchased 2 2 2 Unpacking and inspection of the unit CAUTION Cut and abrasion h...

Page 10: ...avoid injury to people and animals and or damage to property 2 4 Storage Storage of the packed unit The unit must be stored In a covered and dry place Away from heat sources Protected from dirt Protec...

Page 11: ...number 60A _ _0 60A _ _1 60A _ _2 60A _ _3 60A _ _4 60A _ _5 60A _ _6 Fix speed Variable speed PWM control Temperature control Timer control Standby mode Air purge function Error code flashing LED lig...

Page 12: ...l min 6 6 gpm 23 l min 3 Motor control V Variable speed P PWM control only for OEM applications F Fix speed 4 Pump housing material B Brass D Plastic for drinking water NSF 61 compliant S Stainless s...

Page 13: ...tor pump motor 14 Screw 5 32 x1 9 16 4x40 mm 2 pcs 4 Cable gland 15 Plastic anchor 1 4 x1 3 16 6x30 mm 2 pcs 5 Screw ring 6 Ceramic bearing ball 16 Pump housing Sweat code BS 7 O ring 17 Union fitting...

Page 14: ...ated by the piping in the house water supply line and the return line NOTICE Water pressure A recirculating system is a pressurized system operating at the city water pressure as determined by the pre...

Page 15: ...ep the hot water temperature below 140 F 60 C Higher temperatures can cause calcium and magnesium elements to come out of solution and create solids which could not only cause damage to the pump but a...

Page 16: ...t is prohibited to use the unit to pump aggressive liquids acids and seawater DANGER Potentially explosive atmosphere hazard It is prohibited to start the unit in environments with potentially explosi...

Page 17: ...e the pump and the piping is protected from freezing Install in one of the permitted mounting positions see Figure 8 on page 23 Observe the instructions given in the section 8 2 Operating environment...

Page 18: ...he end of the hot water supply line as possible and run the line back to the water heater Decide on the course of the recirculation pipe also determining the length of the pipe required and whether th...

Page 19: ...stall these components With the shut off valve closed at the suction side of the pump and with the check valve installed at the discharge side the screw ring item 5 in Figure 3 can be loosen thus the...

Page 20: ...e unit is supplied with a 6 feet long grounded cord NOTICE The next installation guide applies to most situations where faucets taps are connected to the hot and cold water supply lines with braided f...

Page 21: ...ICE In some older homes the riser shut off valves may be difficult to shut off completely or maybe it is necessary to turn the valves into a different orientation If this is the case shut the water of...

Page 22: ...the shut off valve on the inlet side of the pump and turn the water supply to the house back on 8 Flush system of debris Before reattaching the pump motor open the shut off valve on the inlet side of...

Page 23: ...the concerning instructions in section 4 3 1 Guidelines for the hydraulic system on page 20 21 2 Fasten the Autocirc unit to the wall under the sink using the wall bracket provided in the Autocirc ki...

Page 24: ...replaced 5 Screw on the 9 16 end of the purchased flexible hoses to the outlet connections on the pump housing Screw on the 1 2 end of these same two hoses to the underside of the hot and cold water...

Page 25: ...AUTION Be careful not to damage the internal seal risk of leakage of very hot or cold liquid during the operation of the unit CAUTION The use of PTFE impregnated pipe compound and PTFE tape on pipe th...

Page 26: ...ion 3 Tighten the screw ring When installing the recirculating pump in a horizontal position the timer shall point upwards It may be turned in the range from 10 30 to 13 30 45 at maximum in order to m...

Page 27: ...manner the GFCI is defective If the GFCI interrupts power to the pump without the test button being pushed a ground current is flowing indicating the possibility of an electric shock Do not use this...

Page 28: ...e receptacle Do not use an extension cord If the pump unit is supplied without a power cord use only a UL certified SJTW type PVC insulated and sheathed hard service flexible cord with copper conducto...

Page 29: ...all connections are secure and the conduit box cover is closed before electrical power is connected DANGER Electrical hazard Pumps that do not equipped with standard power supply plug may only be conn...

Page 30: ...structions in section 4 Installation on page 17 have been performed The system has been flushed thoroughly to prevent foreign objects and impurities from blocking the pump The system has been filled a...

Page 31: ...epeat the air purging Figure 15 5 5 Setting the timer To increase the overall efficiency of a hot water recirculating system some pump models are equipped with a plug in timer unit it is also availabl...

Page 32: ...retrofitting If you install the timer as retrofitting follow the instructions of section 4 4 2 Guidelines for electrical connection only point 4 on page 28 and section 4 4 3 Guidelines for timer conn...

Page 33: ...ith a control knob run on a constant speed if energized until reaching the factory preset temperature limit it is around 97 F 36 C as default then the pump stops and switches to standby mode When the...

Page 34: ...as required during the programmed sequence of operation Do not be concerned if the pump does not begin running immediately after the pump is plugged in This just means that there is already hot water...

Page 35: ...d models This algorithm protects the unit from dry running during normal operation This algorithm is a special version of the dry run protection If the expected power level cannot be restored in 3 x 9...

Page 36: ...le working tools WARNING Hot water hazard Before draining the system allow water to cool to at least 100 F 38 C open the drain valve take precautions against water damage and leave the drain valve ope...

Page 37: ...Disconnect the electrical supply lines to the pump Close the valves on the suction and discharge sides of the pump if no valves have been installed it may be necessary to drain the system Loosen the...

Page 38: ...ion the pump is running Continuous on Air purge sequence is active Blinking 200 ms on 200 ms off 200 ms on Standby mode Blinking 50 ms on 1 5 s off 50 ms on Low voltage failure Blinking 1 x short 1 x...

Page 39: ...line Add a check valve on the cold supply line above the return line tee connector If the noise occurs when an Autocirc pump turns off it is likely to be water hammer that results from the closure of...

Page 40: ...tor NOTICE To avoid condensation in the stator or in the electronics the liquid temperature must be higher than the ambient temperature 8 3 Pumped liquid CAUTION This pump has been designed and tested...

Page 41: ...Weight lb kg e3 _V BSPYZ 01 e3 _F BSPQZ 01 e3 _F BSPRZ 01 e3 _F BSPYZ 01 2 2 1 0 e3 _V BSXYZ 01 e3 _F BSXQZ 01 e3 _F BSXRZ 01 e3 _F BSXYZ 01 1 8 0 8 e3 _V BSPYC 01 e3 _F BSPQC 01 e3 _F BSPRC 01 e3 _F...

Page 42: ...kg e3 _V BUPYZ 01 e3 _F BUPQZ 01 e3 _F BUPRZ 01 e3 _F BUPYZ 01 2 6 1 2 e3 _V BUXYZ 01 e3 _F BUXQZ 01 e3 _F BUXRZ 01 e3 _F BUXYZ 01 2 2 1 0 e3 _V BUPYC 01 e3 _F BUPQC 01 e3 _F BUPRC 01 e3 _F BUPYC 01...

Page 43: ...en Original Instructions Installation Operation and Maintenance Manual 43 8 7 Hydraulic curves e3 4F BS__Z e3 4F BT__Z e3 4V BS__Z e3 4V BT__Z e3 4F BU__Z e3 4V BU__Z...

Page 44: ...en Original Instructions 44 Installation Operation and Maintenance Manual e3 6F BS__Z e3 6F BT__Z e3 6V BS__Z e3 6V BT__Z e3 4F BAP_C e3 6V BU__Z...

Page 45: ...Manufacturer applications the pump has customized versions which differ from the standard trade versions in some features An individual PSS Product Specification Sheet document is issued for each of t...

Page 46: ...be disposed of through approved companies specialized in the identification of different types of materials steel copper plastic etc WARNING It is prohibited to dispose of lubricating fluids and other...

Page 47: ...ty void Any parts repaired or replaced under the Warranty are warranted only for the balance of the warranty period on the parts that were repaired or replaced Seller shall have no warranty obligation...

Page 48: ...s other than Seller or without Seller s written approval b subject to misuse misapplication neglect alteration accident or physical damage c used in a manner contrary to Seller s instructions for inst...

Page 49: ...reating innovative solutions to meet our world s water needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move trea...

Reviews: