Fault! <71>R PFC IGBT fault
PFC IGBT over-current in R phase
Fault! <72>S PFC IGBT fault
PFC IGBT over-current in S phase
Fault! <73>T PFC IGBT fault
PFC IGBT over-current in T phase
Fault! <74>R INV IGBT fault
INV IGBT over-current in R phase
Fault! <75>S INV IGBT fault
INV IGBT over-current in S phase
Fault! <76>T INV IGBT fault
INV IGBT over-current in T phase
Fault! <77> ISO Over temp
Isolation transformer over temperature
Fault! <79> Power Module Connect Fail As stated.
Warning! <01> BATT open
Battery not connected
Warning! <02> IP N loss
Input N loss
Warning! <03> IP site fail
Input site failed
Warning! <04> Line phase error
As stated.
Warning! <05> Bypass phase error
As stated.
Warning! <06> Bypass FRE unstable
Bypass frequency unstable
Warning! <07> BATT over charge
Battery over charge
Warning! <08> BATT low
Battery voltage is too low
Warning! <09> Overload warning
As stated.
Warning! <0A> Fan lock warning
As stated.
Warning! <0B> EPO active
As stated.
Warning! <0D> Over temperature
As stated.
Warning! <10> L1 IP fuse fail
L1 Input fuse failed
Warning! <11> L2 IP fuse fail
L2 Input fuse failed
Warning! <12> L3 IP fuse fail
L3 Input fuse failed
Warning! <21> Line connect dif
Line connect different
Warning! <22> Bypass connect dif
Bypass connect different
Warning! <24> Par INV vol dif
Parallel output voltage setting different
Warning! <33> Lock BYP OL 3 times
Locked in bypass after overload 3 times in 30 min
Warning! <34> AC input CURR unb
Three-phase AC input current unbalanced
Warning! <35> Bat Phase loss
Battery phase loss
Warning! <36> INV CURR unb
Inverter current unbalanced
Warning! <3A> maintain is open
Cover of maintain switch is open
Warning! <3B> Auto Adapt Fail
Phase Auto Adapt failed
Warning! <3C> Utility ext unb
Utility extremely unbalanced
Warning! <3D> Bypass unstable
As stated.
Warning! <3E> BATT VOL High
Battery voltage is too High
Warning! <3F> BATT VOL Unbalance
Battery voltage unbalanced
Warning! <40> Charge Short
As stated.
Warning! <41> Bypass Loss
As stated.
Warning! <42> ISO Over temp
Isolation transformer over temperature
Warning! <43> BUS soft Error
BUS soft start failure
Warning! <44> Redundancy Error
As stated.
Warning! <45> cRedundancy OverLoad As stated.
Warning! <46> EEPROM Fail
EEPROM operation error
Warning! <47> STS Lost
STS module loss
Warning! <48> Power module unlock
As stated.