Xtreme Power Conversion Corporation
TX90 6kVA & 10kVA Service Manual
Page 7
Uninterruptible Power Supply
14
Er14
Fan out of order
15
Er15
Wrong Procedure to Enter Maintenance Mode
16
Er16
Output Parameters Set Error in Parallel System
17
Er17
ID Numbers are in conflict in Parallel System or ID number Error
in single unit
18
Er18
EEPROM’s data error. Its values are reset to default.
(Nomral/220V/adj0%/+/-3Hz/low sensitivity)
19
Er19
Reserved
20
Er20
DC Bus voltage can’t be discharged
21
Er21
Parallel communication error (communication wire disconnect-
ed or failure to find ID1 UPS) in parallel system
22
Er22
Bypass SCR or Output Fuse Fails
23
Er23
Inverter Relay or SCR or Output Fuse Fails
24
Er24
Bypass Input found when Running on CVCF mode
25
Er25
Reserved
26
Er26
PFC over-current
27
Er27
The UPS must be operated in normal mode in parallel system
28
Er28
Bypass Overload Time out and cut off output.
29
Er29
Charger Overcharges battery (>300Vdc)
30
Er30
Inverter Balance Error
31
Er31
The settings of both control board and driver board are not
matched each other.
32
Er32
Sync Signal Error
33
Er33
Isolated transformer overheat
34
Er34
Balance function conflict
35
ER35
Output Parallel Failed
36
CEr1
Utility voltage out of range
37
CEr2
Bypass Voltage out of range
38
CEr3
Inverter Voltage out of range
39
CEr4
Load Percentage out of range
40
CEr5
Battery Voltage out of range
41
CEr6
UPS Output Voltage out of range
Remarks:
1. When one of the Er06, EPO, Er23, Er24, Er28, Er32 ,or Er33 error message occurs, the UPS will have no
output and lock itself immediately.
2. If the bypass voltage is normal(within specs), but one of the Er01, Er02, Er03, Er05, Er13, Er14, Er20, Er22,
Er26, Er29 or Er30 error message occur, the UPS will transfer to Bypass loop and lock itself.
3. If the bypass voltage is normal(within specs), one of the Er04, Er08, Er09, Er10, Er11 or Er12 error message
occurs, the UPS will transfer to Bypass loop, then try to transfer back to Inverter mode automatically. If
the symptoms happen 4 times in one hour, the UPS will lock itself; otherwise, the error messages and the
times of the error messages will be clear and reset automatically.
4. If the Er16, Er17, Er21, Er27, Er31 or Er34 error message occurs, the inverter of the UPS will have no output
and the user is prohibited to turn on the UPS from the front panel.