Xtreme Power Conversion Corporation
TX90 6kVA & 10kVA Service Manual
Page 38
Uninterruptible Power Supply
Troubleshooting
If there is a abnormal condition occurred, the LCD display will show an error code as indicated at
Chapter 1. Please follow the troubleshooting indicated below.
Error Code Er01
Definition:
The UPS is in the 1st stage soft start procedure, but the DC bus voltage can not reach 50Vdc within 5
seconds, or can not reach anticipative charging voltage (about either present 80% of battery voltage or present
output voltage of charger) within 30 seconds.
Flow Chart