Troubleshooting 4
2.
2.1
When the indoor unit encounters a recognized error on different models ,
1. the running LED with flash in a corresponding series, the timer LED may turn on or begin flashing;
2. an error code will be displayed;
3. both 1 and 2.
These error codes are described in the following tables:
Running
Lamp
Timer
Lamp
Display
Information
Solution
--
--
F
Defrost
Normal
Display
, not
error code
--
--
CL
Filter cleaning reminder(power on display for 15 seconds)
--
--
CL
Active clean
--
--
F
Filter replacement reminder(power on display for 15 seconds)
--
--
FP
Heating in room temperature under 8°C
--
--
FC
Forced cooling
--
--
AP
AP mode of WIFI connection
--
--
CP
Remote switched off
1 time
OFF
EH 00/EH 0A
Indoor unit EEPROM parameter error
TS01-IDU
2 times
OFF
EL 01
Indoor/outdoor unit communication error
TS02-S-INV
3 times
OFF
EH 02
Zero-crossing signal detection error
TS03
4 times
OFF
EH 03
The indoor fan speed is operating outside of the normal range
TS04-S-IDU
5 times
OFF
EC 51
Outdoor unit EEPROM parameter error
TS01-ODU
5 times
OFF
EC 52
Condenser coil temperature sensor T3 is in open circuit or has short
circuited
TS05-ODU
5 times
OFF
EC 53
Outdoor room temperature sensor T4 is in open circuit or has short
circuited
TS05-ODU
5 times
OFF
EC 54
Compressor discharge temperature sensor TP is in open circuit or
has short circuited
TS05-ODU
5 times
OFF
EC 56
Evaporator coil outlet temperature sensor T2B is in open circuit or
has short circuited(for free-match indoor units)
TS05-ODU
6 times
OFF
EH 60
Indoor room temperature sensor T1 is in open circuit or has short
circuited
TS05-IDU
6 times
OFF
EH 61
Evaporator coil middle temperature sensor T2 is in open circuit or
has short circuited
TS05-IDU
12 times
OFF
EC 07
The outdoor fan speed is operating outside of the normal range
TS04-ODU
9 times
OFF
EH 0
Indoor PCB/Display board communication error
TS07
8 times
OFF
EL 0C
Refrigerant leakage detection
TS06-INV
7 times
FLASH
PC 00
IPM malfunction or IGBT over-strong current protection
TS09-S
2 times
FLASH
PC 01
Over voltage or over low voltage protection
TS10-S
Summary of Contents for MSAGBU-09HRFN8-QRD1GW
Page 1: ...XTREME 3D INVERTER SERIES SM_AG GA _R32_3D INV_EU_NB_2006 SERVICE MANUAL ...
Page 2: ......
Page 5: ......
Page 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions ...
Page 18: ...Outdoor unit wiring diagram 16022000019533 ...
Page 56: ... Outdoor Unit Disassembly 3 2 Dimension 1 Panel Plate AA30 ...
Page 57: ... Outdoor Unit Disassembly 4 2 Panel Plate AB30 ...
Page 58: ... Outdoor Unit Disassembly 5 3 Panel Plate BA30 ...
Page 59: ... Outdoor Unit Disassembly 6 For US models ...
Page 60: ... Outdoor Unit Disassembly 7 4 Panel Plate B30 ...
Page 61: ... Outdoor Unit Disassembly 8 For US models ...
Page 62: ... Outdoor Unit Disassembly 9 5 Panel Plate CA30 ...
Page 63: ... Outdoor Unit Disassembly 10 For US models ...
Page 64: ... Outdoor Unit Disassembly 11 6 Panel Plate D30 ...
Page 65: ... Outdoor Unit Disassembly 12 For US models ...
Page 66: ... Outdoor Unit Disassembly 13 7 Panel Plate X130 ...
Page 67: ... Outdoor Unit Disassembly 14 For US models ...
Page 68: ... Outdoor Unit Disassembly 15 8 Panel Plate X230 ...
Page 69: ... Outdoor Unit Disassembly 16 For US models ...
Page 70: ... Outdoor Unit Disassembly 17 9 Panel Plate X330 ...
Page 71: ... Outdoor Unit Disassembly 18 For US models ...
Page 72: ... Outdoor Unit Disassembly 19 10 Panel Plate X430 ...
Page 73: ... Outdoor Unit Disassembly 20 For US models ...
Page 148: ......