Xtreme Power Conversion Corporation
NXTi 3P-3P User’s Manual
Page 33
Uninterruptible Power Supply
Warning Indicator
Warning
Icon (flashing)
Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beeping every second
Warning Code
Warning code Warning event
Warning code Warning event
01
Battery unconnected
10
L1 IP fuse broken*
02
IP Neutral loss
11
L2 IP fuse broken*
04
IP phase abnormal
12
L3 IP fuse broken*
05
Bypass phase abnormal
21
Line situations are different in parallel
system
07
Over charge
22
Bypass situations are different in
parallel system
08
Low battery
33
Locked in bypass after overload 3
times in 30 minutes
09
Overload
34
Converter current unbalance
0A
Fan failure
35
Battery fuse broken
0B
EPO enable
3A
Cover of maintain switch is open
0D
Over temperature
3C
Utility extremely unbalanced
0E
Charger failure
3D
Bypass unstable
* These alarms are only for the single input unit.