Xtreme Power Conversion Corporation
NXTi 3P-3P User’s Manual
Page 21
Uninterruptible Power Supply
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN
: Bypass allowed. When selected, UPS will run at Bypass mode
depending on bypass enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s not allowed for run-
ning in Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS
: Bypass disabled. When selected, automatic bypass is accept-
able, but manual bypass is not allowed. Manual bypass means us-
ers manually operate UPS for Bypass mode. For example, pressing
OFF button in AC mode to turn into Bypass mode.
09: Battery backup time setting
Interface
Setting
Parameter 3:
000~999:
Set the maximum discharge time from 0 min to 999 min.
UPS will shut down to protect battery if the discharge time arrives
before the battery is under voltage. The default value is 990 min.
DIS: Disable battery discharge protection and backup time will de-
pend on battery capacity.
10: Reserved
Interface
Setting
Reserve for future options.
11: Reserved
Interface
Setting
Reserve for future options.