Xtreme Power Conversion Corporation
NXTi 3P-3P User’s Manual
Page 11
Uninterruptible Power Supply
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not connected.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc:
battery voltage, Hz: input frequency
Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every second
No
Low battery
Beeping once every second
Battery unconnected
Over charge
EPO enable
Fan failure
Over temperature
Charger failure
L1 IP fuse broken
Battery fuse broken
Overload 3 times in 30min
IP Neutral loss
IP phase abnormal
Converter Current unbalance
Inverter Current unbalance
Cover of maintain switch is open
Phase auto adapt failure
Fault