NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 53
SPECIFICATIONS
MODEL
NXRi-6KL
NXRi-10KL
INPUT
Voltage
230 VAC -55% to +30% single phase
Capacity VA (W)
6000 VA (4800 W)
10000 VA (8000 W)
Frequency
50/60 Hz ± 3%
Power Factor
≥ 0.9
9
Harmonic
Distortion
< 5% THD Non-Linear Load
OUTPUT
Voltage
230 VAC (default) configurable to 208/220/240 VAC single
phase ± 1%
Frequency
50/60 Hz ± 0.1
Crest Factor
3:1 at full load
Transfer Time
0 ms
Load Power Factor
0.8
Efficiency
98% ECO Mode (> 90% online mode)
Overload Capacity
110% for 10 min; 130% for 1 min; > 130% for 1 sec
BATTERY
Battery Type
(EBP20)
(20) 12V 9AH
Recharge to 90%
3 hours
4 hours
Backup Time
half / full
18 min / 7 min
12 min / 5 min
Charge Current
2A
PHYSICAL
UPS Dimensions
W x D x H
438 x 580 x 133 mm
(17.2 x 22.8 x 5.2 in)
438 x 668 x 133 mm
(17.2 x 26.3 x 5.2 in)
UPS Unit Weight
17 kg (37.5 lbs)
20 kg (44.0 lbs)
EBP20 Dimensions
W x D x H
438 x 668 x 133 mm (17.2 x 26.3 x 5.2 in)
EBP Unit Weight
63 kg (138.9 lbs)
Input / Output
Hardwired Terminal / Hardwired Terminal
ENVIRONMENTAL Temperature
0 - 40
°
C (32-104
°
F)
Humidity
0 – 95% Non-Condensing
Audible Noise
< 55dba @ 1 meter
Altitude
3500 m (11,500 ft) above sea level
Approvals
CE, EN/IEC 62040-2, EN/IEC 62040-1, RoHS Compliant
Communication Interface
USB/RS232, EPO, SNMP (optional)
Included with unit
User Manual, monitoring software CD, USB cable
Available Options
SNMP Card, AS-400 Card, EBP20, Rail Kit