NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 43
12: Hot standby function enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose the
following two options in
Parameter 3:
YES:
Hot standby function is enabled. It means that the current UPS
is set to host of the hot standby function, and it will restart after AC
recover y even without battery connected.
NO:
Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery.
13: Battery Voltage Adjustment
Interface
Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery
voltage to real figure.
Parameter 3:
the voltage range is from 0V to 5.7V, the default
value is 0.09V.
14: Charger Voltage Adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger voltage
Parameter 3:
the voltage range is from 0V to 7V, the default value
is 1.1V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
*We strongly suggest using the default value (0). Any modification
should be suitable to battery specifications.
15: Output Voltage Adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter voltage
Parameter 3:
the voltage range is from 0V to 6.4V, the default value
is 0V.