Uninterruptible Power Supply
LCD Message
Explanation
Solution
Warning
0D:LineFuseOpen
Fuse is broken.
Turn off UPS and replace a good one with the bro
‐
ken one. If UPS fails again after you do this, con
‐
tact the service personnel.
Warning
0E:IICEepromFail
EEPROM operation error
Contact service personnel.
Warning 11:Bypas
‐
sIpNLoss
Neutral loss.
Check if the Neutral connection is well
and contact service personnel.
Warning 12:BpsPhas
‐
eError
Bypass phase error.
Check if the Bypass phase sequence is
correct and contact service personnel.
Warning 13:BpsVoltEr
‐
ror
Bypass voltage error.
Check the wiring or contact service personnel
Warning 14:BpsPhase
‐
Fail
As stated.
Contact service personnel
Warning 15:OverLoad In line mode, the connected
devices are demanding more
power than the UPS can supply.
Reduce some load and check output
Load-Capacity in specification.
Warning 16:OverLoad
‐
Lock
The connected devices are de
‐
manding more power than the
UPS can supply. UPS will transfer
to bypass mode from line mode.
Reduce some load and check output
Load-Capacity in specification.
Warning 17:EpoActive Check the EPO connector.
Check if the connector is loose when EPO
acts abnormally.
Warning 18:Main
‐
tainOpen
The UPS is in maintenance
mode.
Check if the 2-pin plate is not connected
to EMBS connector on the back panel of communi
‐
cation module when it acts abnormally.
Warning 19:LineDiff
Each module gets different line
voltage when they are in parallel.
Contact service personnel.
Warning 1A:BypassDiff Each module gets different
bypass voltage when they are in
parallel.
Contact service personnel.
Warning
1B:InvCurUnbal
As stated.
Contact service personnel.
Warning
1C:BpsUnstable
UPS switches between bypass
mode and standby mode five
times in 30 minutes due to ab
‐
normal utility.
Contact service personnel.
Warning
1D:RedundancyFail
As stated.
Check if redundancy setting is correct or
not. Then, contact service personnel.
Warning! Battery Age
Alert
Battery life is expired.
Check if the battery has been used over
its service age. Or contact service personnel.
Warning! Dry Contact
Input Alarm 1
As stated.
Remove the node
Warning! Dry Contact
Input Alarm 2
As stated.
Remove the node