Xtreme Power Conversion Corporation
M90S Service Manual
Page 24
Uninterruptible Power Supply
LCD Message
Explanation
Solution
Fault 34:Ver Incompat The firmware version between
UPS modules is incompatible.
Contact service personnel.
Fault 41:DSP Comm
Fail
The internal communication in
UPS module is interrupted.
Contact service personnel.
Fault 42:Over load
Heavy overload causes UPS fault. Reduce some load.
Fault 43:Charger Fail
Battery polarity is connected
reversely or charger voltage is
abnormal.
Contact service personnel.
Fault 44:Model Fault
UPS model is not able to identify.
Contact service personnel.
Fault 45:Mcu Comm
Fail
As stated.
Contact service personnel.
Fault 46:CT Satiation
Load current sensor is abnormal.
Contact service personnel.
Fault 47:Fan Fault
The two fans are stuck or broken. Make sure fans work well when UPS is
working.
Warning 01:BatLow
Battery voltage is low.
Charge the battery when the mains is normal.
Warning 02:BatOpen
Battery is not connected.
1. Check battery breaker status.
2. Check if the battery connection is well con
‐
nected.
3. Check the setting of Nominal Battery voltage.
4. Contact service personnel if necessary
Warning 03:Bat
‐
PhaseLoss
The voltage between positive
and negative battery is different.
Check the battery connection.
Warning 04:Lin
‐
eIpNLoss
Neutral loss
Check if the Neutral connection is well and contact
service personnel.
Warning 05:LinePhas
‐
eError
As stated.
Check if the Mains phase sequence is
correct and contact service personnel.
Warning 06:LineVolt
‐
Error
As stated.
Check if the input wiring is correct or
contact service personnel
Warning 07:Line
‐
PhaseFail
As stated.
Check if the input wiring is correct or contact ser
‐
vice personnel
Warning 08:Over
‐
Charge
Battery voltage is too high.
Check the setting of Nominal Battery
voltage and contact service personnel.
Warning 09:ChgFail
Battery voltage is detected as
low level.
However, the charge is able to
work.
Contact service personnel.
Warning 0A:OverTemp The temperature in UPS is higher
than 75°C. At this time, the
UPS is still running.
Check if the ambient temperature is over
specification.
Or contact service personnel.
Warning
0B:PFCCurUnbal
PFC current is unbalance.
Contact service personnel
Warning 0C:FanError
Fan error.
Check if the fan is blocked or contact
service personnel.