background image

BP-XR4U480A

External Battery Pack

User & Installation Manual

www.xpcc.com

 

| © 2016 Xtreme Power Conversion Corporation. All rights reserved. (Rev 6/22/16)

Summary of Contents for BP-XR4U480A

Page 1: ...BP XR4U480A External Battery Pack User Installation Manual www xpcc com 2016 Xtreme Power Conversion Corporation All rights reserved Rev 6 22 16 ...

Page 2: ...oduct Overview 3 Assembly 3 Dismount the Cabinet Shell 3 Battery Installation and Connection 5 Fuse in Battery Pack 6 4 Post Rail Mounting 7 Multiple Battery Pack Connections 7 Installation and Setup 8 Unpacking Inspection 8 Selecting Installation Position 8 Enclosure Installation 9 Battery Module Installation 9 ...

Page 3: ...breaker fuse terminal etc with a maximum capacity of 40 pcs CSB UPS12580 batteries inside The battery connection could be configured to output 240V two groups batteries connect in series as BAT N BAT Complete BP XR4U480A cabinet Assembly Dismount the Cabinet Shell Put the battery pack on a level pull of bolts at the right side battery tray than pull out the battery tray remove the battery tray top...

Page 4: ...Xtreme Power Conversion Corporation BP XR4U480A User s Manual Page 4 External Battery Pack ...

Page 5: ...allation and Connection Users need 40 pcs batteries divide into 2 groups Each group has 20 pcs batteries in series as BAT N BAT shown below 40 pcs batteries installation and connection Each battery tray fit 10pcs batteries then connect the batteries as shown in below pictures 40pcs batteries installation ...

Page 6: ...correct with multi meter or other equipment Install the cover if the voltages are correct Note Battery poles cannot be reversed also cannot short the battery poles otherwise batteries would be damaged or other accidents would happen Don t touch the battery poles at the same time It s better only single man make the operation Fuse in Battery Pack The battery pack has 2 x fuses inside as shown in be...

Page 7: ... batteries with different capacity or dif ferent brands or new or old batteries WARNING ENSURE CORRECT POLARITY OF STRING END CONNECTIONS TO THE BATTERY CIRCUIT BREAKER AND FROM THE BATTERY CIRCUIT BREAKER TO THE UPS TERMINALS I E TO TO N TO N DISCONNECT ONE OR MORE BATTERY CELL LINKS IN EACH TIER DO NOT RECONNECT THESE LINKS AND DO NOT CLOSE THE BATTERY CIRCUIT BREAKER UNLESS ALL CONNECTIONS ARE ...

Page 8: ...ackaging Note The battery modules are very heavy be cautious when unpacking and lifting the unit to avoid injury Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery system and extend the life of the batteries Please follow the instructions below 1 Do not block the air flow to the ventilatio...

Page 9: ...with screws at front and rear 3 Slide the battery enclosure from the front into the rack onto the shelf kit 4 Fasten front and rear mounting ears to battery enclosure 5 Attach the mounting ears of the battery enclosure into the shelf kit and rack with screws at front and rear Battery Module Installation 1 Remove front cover from the battery enclosure 2 Slide in battery modules 3 Secure front cover...

Reviews: