Uninterruptible Power Supply
Setting - Battery
Displays: Battery Parameter Settings Page.
The following parameters can be adjusted:
Battery Setting
Range
Default
Number (Battery Cells Per String)
192, 204, 216, 228, 240
240
Capacity (Battery Rating AH)
7-200
7
Boost Charge
Enable/Disable
Enable
Group (Battery Strings Qty)
1 to 8
1
V-Boost (Boost Upper Limit Voltage V/cell)
2.41 - 2.50
2.45
V-Float (Float Base Voltage V/cell)
2.20 - 2.29
2.27
V-EOD (EOD Voltage V/Cell)
1.55 - 1.75
1.67
I-MaxCharge (Max Charging Current)
1 - 6
2
Setting - Parallel
Displays: Parallel Parameter Settings Page.
The following parameters can be adjusted:
Parallel Setting
Range
Default
ID
1 to 4
1
Number
1 to 8
2
Redundancy Number
0 to 1
0