Xtralis Pty Ltd
XCC Product Guide
www.xtralis.com
7
2.2
XCC-010 with Capillaries
For the given pipe lengths and number of capillary pipes use hole sizes as defined in Table 2-3 or Table 2-4.
All capillaries are to be the same length and evenly spaced along the pipe (+/- 20%).
The internal diameter of the capillary tube must be 8mm.
Each capillary must be capped and drilled to the holes sizes specified below.
Capillary lengths may be in the range 0.25m to 4m.
Table 2-3: Pre-engineered pipe networks for XCC-010 with capillaries - single pipe
Pipe
Style
Length
(m)
Number of Capillaries / Pipe
3
4
5
6
7
8
9
10
11
12
Single
Pipe
60-80
n/a
n/a
n/a
n/a
n/a
1-3=
3mm
4-6=
3.5mm
7=
4mm
8=
4.5mm
1-4=
3mm
5-8=
3.5mm
9=
4.5mm
1-6=
3mm
7-9=
3.5mm
10=
4mm
1-6=
3mm
7-10=
3mm
11=
4mm
1-3=
2.5mm
4-7=
3mm
8-11=
3.5mm
12=
4mm
Single
Pipe
40-60
n/a
n/a
n/a
all=
3.5mm
all=
3.5mm
all=
3.5mm
all=
3.5mm
1-6=
3mm
7-10=
3.5mm
1-6=
3mm
7-11=
3.5mm
1-4=
2.5mm
5-12=
3mm
Single
Pipe
<40
n/a
all=
3.5mm
all=
3mm
all=
3.5mm
all=
3.5mm
all=
3.5mm
all=
3.5mm
1-6=
3mm
7-10=
3.5mm
1-6=
3mm
7-11=
3.5mm
1-4=
3mm
5-12=
3.5mm
Fire Alarm
Threshold Setting
n/a
IV
IV
III
II
II
I
I
I
I
Table 2-4: Pre-engineered pipe networks for XCC-010 with capillaries - single branch
Pipe Style
Branch Length
Number of Capillaries / Branch
3
4
5
6
Single Branch
40-50
n/a
n/a
all=
4mm
2x
1-2=3.5mm
3-6=4mm
Single Branch
30-40
n/a
all=4.5mm
all=4mm
all=3.5mm
Single Branch
<30
all=4.5mm
all=4.5mm
all=4mm
all=3.5mm
Fire Alarm Threshold Setting
III
II
I
I
Examples:
l
For a single pipe, 65m long with 9 capillaries, the first four capillaries (nearest the detector) should have
a 3mm hole drilled at the capillary end, the last capillary should be 4.5mm and the remaining 4 cap-
illaries (No’s 5-8) drilled 3.5mm. All capillaries should be the same length (within the range 0.25 to 4m
long).using tube with an internal diameter of 8mm.
l
For a system with two 50m long pipes (i.e. a single branch), each with 5 capillaries (10 in total) 8in total)
drill all holes 4mm. All capillaries should be the same length (within the range 0.25 to 4m long).using
tube with an internal diameter of 8mm.
Summary of Contents for XCC-010
Page 1: ...Xtralis Class C XCC Product Guide XCC 010 XCC 01000 MRN May 2011 D N 14159_07 P N 29185 ...
Page 2: ......
Page 6: ...XCC Product Guide Xtralis Pty Ltd iv www xtralis com This page is intentionally left blank ...
Page 8: ...XCC Product Guide Xtralis Pty Ltd 2 www xtralis com This page is intentionally left blank ...
Page 14: ...XCC Product Guide Xtralis Pty Ltd 8 www xtralis com This page is intentionally left blank ...
Page 24: ...XCC Product Guide Xtralis Pty Ltd 18 www xtralis com This page is intentionally left blank ...
Page 26: ...XCC Product Guide Xtralis Pty Ltd 20 www xtralis com This page is intentionally left blank ...