11 Maintaining and Servicing the Detector
To maintain the VESDA VLC-EX detector at its peak performance the maintenance schedule given below
should be followed. Maintenance can be conducted by the original installer, a VESDA distributor, or an
authorized service contractor. To work effectively the VESDA VLC-EX detector needs to be supported by a
well designed pipe network. The VESDA Maintenance Guide contains a schedule for pipe network
maintenance. More frequent maintenance may be necessary for harsh environments or be required by the
local fire authority.
Table 11-1: Maintenance schedule for VESDA VLC-EX detector
Maintenance Check
Quarterly
Six
Monthly
Annually
Biennial
Power Supply
X
Visually Inspect Pipe Network
X
Filter Inspection
X
Pipe Integrity Smoke Test
X
Check Pipe Flow
X
Clean Sampling Point
X
Flush Pipe Network
X
Caution:
When a VESDA VLC-EX detector has been isolated, no fire warnings will be issued by the VESDA
VLC-EX and any fire will go undetected. Prior to any maintenance or testing:
l
Inform appropriate supervising authority about the risk associated with isolating a VESDA
detector.
l
Ensure that any ancillary devices dependent on the VESDA VLC-EX is/are isolated before
work is begun.
Note:
Since the VLC-EX is designed to be applied in an environment where there is potentially a
hazardous atmosphere, it is important that all users are aware of and follow the guidance given in
the appropriate standards, including in: EN 60079-17:2007, “Explosive atmospheres. Electrical
installations inspection and maintenance” and that they also adhere to the specific rules and
regulations for the site where the product is deployed.