VESDA by Xtralis
VESDA VLC-EX Product Guide
www.xtralis.com
11
3.4
Default Settings
Table 3-3: Default values for the VESDA VLC-EX detector
Parameter
Default Values
Range
Access Level
Minimum
Maximum
Event Log - Events
l
Smoke Level
Enabled
N/A
N/A
Adm
l
Alarms
Enabled
N/A
N/A
Adm
l
Faults
Enabled
N/A
N/A
Adm
l
User Action
Enabled
N/A
N/A
Adm
Fire Threshold
0.2% obs/m
(0.062% obs/ft)
0.015% obs/m
(0.0046% obs/ft)
20% obs/m
(6.25% obs/ft)
Adm
Pre-Alarm Threshold
0.14% obs/m
(0.044% obs/ft)
0.010% obs/m
(0.0031 obs/ft)
1.995% obs/m
(0.6234% obs/ft)
Adm
Alert Threshold
0.08% obs/m
(0.025% obs/ft)
0.005% obs/m
(0.0015% obs/ft)
1.990% obs/m
(0.6218% obs/ft)
Adm
Alarm Delays…Fire
10 Seconds
0 Seconds
60 Seconds
Adm
Alarm Delays…Pre-
Alarm
10 Seconds
0 Seconds
60 Seconds
Adm
Alarm Delays…Alert
10 Seconds
0 Seconds
60 Seconds
Adm
Delay Times
Simultaneous
Simultaneous
Cumulative
Adm
Instantaneous Fire
Disabled
N/A
N/A
Adm
AutoLearn
14 days
0 Hours
0 Minutes
0 days
0 Hours
15 Minutes
15 days
23 Hours
59 Minutes
Adm
Air flow Thresholds:
l
High Urgent
l
High Minor
l
Low Minor
l
Low Urgent
l
130%
l
120%
l
80%
l
70%
l
105%
l
105%
l
25%
l
25%
l
200%
l
200%
l
95%
l
95%
Adm
Communications:
l
Open-ended loop
l
Preferred Port
l
Network Delay
l
Health Check
l
None
l
A
l
15 seconds
l
45 seconds
l
N/A
l
N/A
l
10 seconds
l
40 seconds
l
N/A
l
N/A
l
45 seconds
l
60 seconds
DST
Device ID
Name/Location
N/A
N/A
Adm
Faults Latched
Latched
N/A
N/A
Adm
Filter Service Interval
731 days (2 years)
1 day (Dependent
up on environment)
3655 days (10
years)
Adm