ADPRO
XO I/O Interface USB Module – Technical Manual
32688_02
15
4.
Select the desired set number for the module in the
Device Node
column.
5.
Click
Apply Configuration
.
The message
Are you sure to apply your configuration?
appears.
6.
Click
Apply
.
The
Waiting to apply…
message appears.
7.
Wait for the message to disappear.
8.
If you are mapping a double module, repeat for the second module: connect it to the XO device using the
USB cable, click
Refresh
in the configuration tool, and map the module to the correct set number.
9.
If the
Product
columns shows any other devices (in the example screen above, the FT232 USB Serial = an
RS-485-to-USB converter), make sure that these devices are also mapped to a suitable USB port.
10. Click
Logout
.
11. Restart the XO device.
The XO client will not discover the I/O cards until you have restarted the device.
12. Open the XO client and check if the added module is visible in the
I/O
window: choose
System
>
Connections
>
I/O
. For example, if you have added a single module to serve as a second set of I/O cards,
you will see a second line indicating
2-I/O card + ext
.
13. If there were other devices in the hardware mapping list, then:
o
Check their serial ports settings (
System
>
Connections
>
Serial Ports / PTZ
).
o
Test all related functionality (PIR detectors, analogue PTZ camera, modem…).