background image

Xtralis 

VESDA

® 

Xtralis VESDA LCD Programmer Product Guide

www.xtralis.com

35

109.

Address Control

 - The four functions under Address Control are the same as the 

functions performed by the buttons on the Display Module.

Mode -  This controls the mode of the LCD Numerical display on the Display. 
Use the +, -, and the

key to change the mode 

-

Current Sector - Display the First Alarm Sector in VLS Display

-

Sensitivity - Displays the sensitivity level

-

Smoke Level - Displays the current smoke level

-

Address Number - Displays the assigned VESDA Zone number for the 
detector

Silence - Silences beeping sound of the detector

Scan - Selecting this option in a VLS Display commences a Scan sequence of 
the assigned VLS Detector

Reset - Resets faults

Isolate - Starts and stops isolation of the detector

USR

110.

Address Number

 - Assign the VESDA Zone number to a Display/Relay.

ADM

111.

Location

 - Allocate a VESDA Zone name and location and assign these to the 

respective Display/Relay.

ADM

112.

Power Supply Number 

- Input the number of the power supply that is assigned to 

the detector. If the VESDA Intelligent Power Supply is not being used enter “0”.

ADM

113.

Button Lockout

 - This screen provides the option to Lock or enable the buttons on 

a Display.

ADM

114.

Relays/Disp Connected -

 Use the screen to enter the number of relays connected 

to the Display. It also indicates if the detector is a VLS.

DST

115.

Relay Setup

 - This displays sub-menus for:

Relay Startup Mode (only used on a display with relays assigned)

Latching

Beeper

Relay Assignments (only used on a display with relays assigned)

ADM

116.

Relay Startup Mode

 - Displays the energize/de-energized condition for each relay. 

If required, use the 

+ -

 and

keys to change the energized/de-energized state of 

relays. 

ADM

Scrn
No.

Description

Min. 
Access 
Level 

Parameter

Default

Relay Startup Mode

Relay 2 & 3 energized

Energized

Relays 1, 4-7 (4-12)

De-Energized

Summary of Contents for LCD Programmer Module

Page 1: ...Xtralis VESDA LCD Programmer Product Guide Document Number 10194_05 Part Number 30004...

Page 2: ......

Page 3: ...cause equipment damage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only pe...

Page 4: ...ion Convention Description Caution This icon is used to indicate that there is a danger to equipment The danger could be loss of data physical damage or permanent corruption of configuration details W...

Page 5: ...ent power circuit to the receiver or consult the dealer or an experienced radio television technician for help FDA This VESDA product incorporates a laser device and is classified as a Class 1 laser p...

Page 6: ...Xtralis VESDA LCD Programmer Product Guide Xtralis VESDA iv www xtralis com...

Page 7: ...cess Level 6 Personal Identification Number PIN 7 Hour Glass Symbol 7 5 Installing and Connecting the LCD Programmer 7 Installing an LCD Programmer in a Detector 7 Installing an LCD Programmer in a Re...

Page 8: ...Xtralis VESDA LCD Programmer Product Guide Xtralis VESDA 2 www xtralis com...

Page 9: ...ugh VESDAnet The Xtralis VESDA VLC 500 RO System Relay Module and AOM cannot be programmed using the LCD Programmer The programmer enables management and interrogation of Xtralis VESDA devices connect...

Page 10: ...plate of a VLP or VLS detector Front Cover or in an Xtralis VESDA Remote Mounting System For further information see the Xtralis VESDA Remote Systems Product Guide Figure 2 The Hand held LCD Programme...

Page 11: ...SR Operator ADM Administrator DST Distributor Security Access 3 character User Level ID 4 digit individual Personal Identification Number PIN Default PIN is available with Xtralis VESDA Distributors O...

Page 12: ...t people to access different sets of functions The functions that can be edited with USR ADM and DST access levels are listed in LCD Programmer Screen Description on page 13 Table 2 User access levels...

Page 13: ...data is received by the LCD Programmer if there is a large amount of information transferred to the LCD programmer this may take several minutes 5 Installing and Connecting the LCD Programmer Installi...

Page 14: ...logs you off it will display a warning message and beep Press any key on the programmer to stop the detector from automatically logging you off Key Key Type Description Used For Soft Directional Key S...

Page 15: ...programmer menu 1 of 4 34 Latching 1 Main Menu 2 Logon 3 VLP Detector 4 Setup By Zone 6 VLP Detector 138 Setup By Type 5 Zone Number and Name 7 Status 8 Event Log 9 View Events 10 Select Events 11 Zon...

Page 16: ...eekend 53 Holidays 58 Smoke Change 54 Scanner 55 Scanner Delays 56 Sector Factor 57 Valve Operations 59 AutoLearn 60 Zone Number 61 Zone Name Location 62 Air Flow 65 Normalize 66 Filter 63 Flow Thresh...

Page 17: ...Filter 94 Flow Thresholds 97 Reference Detector 98 Rebuild Zone List 99 Power Supply Number 100 Button Lockout 101 Diagnostics 102 Relay Test 103 Factory Defaults 104 Communications 105 Miscellaneous...

Page 18: ...Miscellaneous 132 HLI 133 Status 134 Location 135 Power Supply Number 136 Factory Defaults 137 Communications 140 System All Device 141 Status 142 System Control 143 AutoLearn 144 Set Date Time 145 W...

Page 19: ...ESDA Zone numbers and names are allocated this screen lists all the VESDA Zone numbers and names on VESDAnet All devices without a VESDA Zone number are grouped in an unconfigured devices menu The Anc...

Page 20: ...der Zone Address control are the same as the functions performed by the buttons on the display module Mode This controls the mode of the Multi Segment LCD display on any display connected to that zone...

Page 21: ...evant week day will denote it as being weekend By default Saturday and Sunday are set as weekend days ADM 18 Holidays Insert the first and the last day of holidays to set the different smoke threshold...

Page 22: ...detector ADM 23 Air Flow This screen lists the options available to monitor and manage air flows Flow Thresholds Flow Control Normalize ADM 24 Flow Thresholds Input the required High Urgent High Minor...

Page 23: ...DST 28 Reference Detector If a reference detector is connected to VESDAnet enter the Reference Address Number Dilution Factor This is the factor by which the background levels have to reduce to reach...

Page 24: ...o be reported even after the event is over Manual intervention is necessary to reset If the condition is unlatched the reporting of the condition automatically stops once the event is over To latch an...

Page 25: ...restore factory defaults highlight Restore and press Defaults OK Highlighting Start and pressing will acknowledge Factory Default settings and clear faults 12 30 31 33 34 35 38 57 68 and 72 DST ADM 3...

Page 26: ...Displays the current Status of the Address Smoke Level Displays the current smoke level in the VESDA Zone Alarms If the detector is in alarm mode the alarm stage is displayed Faults List of faults gen...

Page 27: ...ce a and key to insert a x to deselect the option ADM DST 47 Address Control The four functions under Address Control are the same as the functions performed by the buttons on the Display Module Mode...

Page 28: ...urday and Sunday are set as weekend days ADM 53 Holidays Insert the first and the last day of holidays to set the night fire thresholds during this period ADM 54 Scanner The Scanner Menu has 3 sub men...

Page 29: ...s air sample from a previous pipe to clear out from the detector before it starts reading the air sample from the next pipe Thresholds The smoke threshold for the VLS Day Threshold The day smoke thres...

Page 30: ...nt log This is subject to the change occurring over the interval period that is input You can input the required obscuration and interval Change By Min Interval ADM DST Scrn No Description Min Access...

Page 31: ...d be monitored above and below the threshold levels An appropriate urgent or minor air flow fault will be generated once the air flow crosses the threshold and remains above or below the threshold for...

Page 32: ...nce detector These settings allow you to fine tune how much of the smoke detected by the reference detector is also likely to reach each detector Delay The amount of time it will take smoke to move fr...

Page 33: ...lt continues to be reported even after the event is over Manual intervention is necessary to reset If the condition is unlatched the reporting of the condition automatically stops once the event is ov...

Page 34: ...ondition Fault Test This causes a system fault for 30 seconds Flow Fault This causes a 30 second Air Flow fault Sector Test This allows all valves to be forced closed and open Scan Test This will perf...

Page 35: ...or details on GPI functions please refer to the VLS Product Guide ADM DST 80 VLC Detector Lists functions available for accessing and managing the properties of the selected VLC detector Select the re...

Page 36: ...g of events highlight Start and press Note Use the key to place a and key to insert a X and deselect the option ADM DST 85 Address Control The four functions under Address Control are the same as the...

Page 37: ...er the interval period that is input You can input the required obscuration and interval Change By Min Interval ADM DST Scrn No Description Min Access Level Parameter Default Minimum Maximum Fire 1 Fi...

Page 38: ...Input the required High Urgent High Minor Low Minor and Low Urgent air flow thresholds Enter the time over which the air flow should be monitored above and below the threshold levels An appropriate ur...

Page 39: ...lso likely to reach each detector Delay The amount of time it will take smoke to move from the reference detector to the other detectors ADM 98 Rebuild Address List Highlight start and press to rebuil...

Page 40: ...s that the device is set to meet UL specifications Latch Alarms This provides a YES NO option to latch unlatch all Alarms Latch Faults This provides a YES NO option to latch unlatch all Faults GP Inpu...

Page 41: ...Display Relay ADM 111 Location Allocate a VESDA Zone name and location and assign these to the respective Display Relay ADM 112 Power Supply Number Input the number of the power supply that is assigne...

Page 42: ...el or fault The isolate function is fixed for unlatched and cannot be changed ADM 118 Beeper Placing a tick beside each of the fire and fault conditions will result in the beeper activating during thi...

Page 43: ...n allows settings for Net Delay This function sets the maximum time for a message to travel around the network and return to the originating device If the message does not return within the prescribed...

Page 44: ...cate a VESDA Zone name and location and assign these to the LCD Programmer ADM 127 Power Supply Number Input the number of the power supply that is assigned to the detector If the VESDA Intelligent po...

Page 45: ...during production Sub Node Type Informs the type of HLI connected to VESDAnet USR 134 Location Allocate a VESDA Zone name and location and assign these to the LCD Programmer ADM 135 Power Supply Numbe...

Page 46: ...Sector Display the First Alarm Sector in VLS Display Sensitivity Displays the sensitivity level Smoke Level Displays the current smoke level Address Number Displays the assigned VESDA Zone number for...

Page 47: ...nd below the threshold levels An appropriate urgent or minor air flow fault will be generated once the air flow crosses the threshold and remains above or below the threshold for the period set as Del...

Page 48: ...vices on the system are set to meet UL specifications Isolate Remind Provides an option to enable or disable the reminder beeper when the Isolate function is enabled Support Displays the contact phone...

Page 49: ...0 21 29 30 Alarms Status 13 Alert 31 Alert level 15 Ancillary Devices 34 AutoLearn 16 25 32 VLP Detector 40 Automatic Log Off 8 B Backward Action Key 8 Beeper 36 Button Lockout 33 35 System All Device...

Page 50: ...es 41 Fire 31 Fire 1 15 Fire 2 15 Flow Control 17 25 Flow Fault 28 33 Flow Thresholds 16 25 32 Forward Action Key 8 G GP Input 20 29 34 H Hard Keys 6 Health Check 19 34 37 Communications HLI 39 Commun...

Page 51: ...t Threshold 23 Night Thresholds 22 Smoke Thresholds VLP Detector 15 Normalize 17 25 32 O Open ended 19 37 Communications HLI 39 Communications LCD Programmer 39 Operating Temperature 5 Overlay Alert 3...

Page 52: ...All Devices 42 Smoke Level 14 20 21 29 30 35 Smoke Level Status 13 Smoke Thresholds 14 21 30 31 Soft Keys 6 Software Version Installed 38 Standby Mode 7 Status 20 29 34 38 HLI 39 System All Devices 4...

Page 53: ...e 14 Smoke 14 Smoke Level 14 Smoke Level Status 13 Smoke thresholds 14 Status alarm 13 Status Cfg Code 13 Status Current flow 13 Status Faults 13 Status Isolated 13 Status SW Version 13 SW Version sta...

Page 54: ...22 Sector Factor 24 Sector test 28 Sector time 23 Select Events 21 Silence 21 Smoke Change 24 Smoke level 20 21 Smoke Thresholds 21 Status 20 SW Version 20 Thresholds 23 UL Version 29 User Action 21...

Reviews: