Xtralis VESDA LCD Programmer Product Guide
Xtralis
VESDA
®
30
www.xtralis.com
84.
Select Events
- This function assists in easier viewing of the logged events. The
events can be sorted as per the categories displayed. After selecting the events,
proceed to Screen 83 to view the events.
•
End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
•
End Time - This is the time up to which events will be displayed for viewing. You
can input the required time in the time field.
•
Events to view -
-
Smoke Level - A
against Smoke Levels will display logged smoke levels
-
Alarms - To display a log of alarms place a
against alarms
-
Faults - Inserting a
against Faults will list all the logged faults
-
User Action - To view a log of user actions place a
against User Action
-
Clear Log - To clear the log of events highlight Start and press
.
Note:
Use the + key to place a
and - key to insert a X and deselect the option.
ADM
DST
85.
Address Control
- The four functions under Address Control are the same as the
functions performed by the buttons on the Display Module.
•
Mode - This controls the mode of the LCD Numerical display on the Display.
Use the +, -, and the
keys to change the mode
-
Sensitivity - Displays the sensitivity level
-
Smoke Level - Displays the current smoke level
-
Address Number - Displays the assigned VESDA Zone number for the
detector
•
Silence - Silences beeping sound of the detector
•
Reset - Resets faults
•
Isolate - Starts and stops isolation of the detector
USR
86.
Smoke Thresholds
-This screen lists sub-menus for:
•
Smoke Thresholds
•
Alarm Delays
•
Smoke Change
USR
Scrn
No.
Description
Min.
Access
Level
↵
Parameter
Default
Minimum
Maximum
Select Events
end date
end time
Selectable
Selectable
Selectable
Selectable
Selectable
Selectable
Events to View
Smoke Level
Alarms
Faults
User Action
Enabled
Enabled
Enabled
Enabled
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
↵