Fan Settings. 

 

SPEED SETTING 

The fans are factory set to low speed, but have two speed settings for different applications. Select either high or low speed 
by connecting the jumper between the centre and high or low speed pin on the jumper (see Figure G). 

 
DX100TR / DX100TS / DX100PIRR / DX100PIRS only. 

 

To adjust the over-run period turn the control (T) clockwise to increase and anti-clockwise to decrease – see Figure F.

 

 
DX100HTR / DX100HTS / DX100HPTR / DX100HPTS only – see figures F and G. 

 

The  pre-set  humidity  operation  is  factory  set  at  approximately  75%  Relative  Humidity  (RH),  but  can  be  adjusted 
between 65% and 85% RH by control H. 

 

The over-run timer is factory set at 15 minutes but can be adjusted from 30 seconds to 30 minutes by control T. 

 

Turn the controls clockwise to increase RH or time and anti-clockwise to decrease. 

 

 
Using the fan. 

 
DX100R / DX100S Only 

 

Operate the fan using the on/off switch (not supplied). Repeat to switch off. 

 

DX100TR / DX100TS Only 

 

Operate the fan using an on/off switch (not supplied). Note – the fan may take up to 10 seconds to turn on once the 
switch has been operated. When the switch is turned off, the fan continues to operate for the set time delay. To adjust 
the over-run period, turn the control “T” clockwise to increase and anti-clockwise to decrease – see Figure F. 

 

 

 

 

 

Summary of Contents for DX100R

Page 1: ... install each fan with a means for disconnection in all poles in the fixed wiring Do make sure the mains supply is switched off before attempting to make electrical connections or carry out any maintenance or cleaning Please leave this leaflet with the fan for the benefit of the user UK customers If you have any queries before or after installing this product call the Xpelair Technical Hotline 44 ...

Page 2: ...PTR DX100HPTS Operates when triggered automatically by the integral humidity sensor by using an external on off switch not supplied or by using the integral pull cord switch In automatic mode The built in timer automatically operates the fan for the pre set delay time from 30 seconds to 30 minutes once humidity drops below the pre set Relative Humidity RH value External operation When switched off...

Page 3: ...Back plate fixing positions Front Cover Removal Depress Cover Latch with tool remove Cover A C B ...

Page 4: ...Minimum 30 seconds Maximum 30 minutes Factory settings Timer 15 minutes RH 75 D E F ...

Page 5: ...Wiring and setting up G1 ...

Page 6: ...Wiring and setting up G2 ...

Page 7: ...G3 ...

Page 8: ...e centre of the hole As far away as possible from and opposite to the main source of air replacement to ensure airflow across the room e g opposite the internal doorway Near the source of steam or odours Not where ambient temperatures are likely to exceed 50 C If installed in a kitchen fans must not be mounted immediately above a cooker hob or eye level grill If installing in a room containing a f...

Page 9: ...c wall tube onto the ribbed gasket Cut the tube to the required size first if necessary 9 Feed the mains cable through the cable entry hole in the back plate to the terminals 10 Insert the fan tube into the wall duct ceiling as before 11 Fasten the back plate to the wall ceiling using appropriate fasteners supplied See figure A 12 If using screws do not over tighten Mount the back draft shutter 13...

Page 10: ...75 Relative Humidity RH but can be adjusted between 65 and 85 RH by control H The over run timer is factory set at 15 minutes but can be adjusted from 30 seconds to 30 minutes by control T Turn the controls clockwise to increase RH or time and anti clockwise to decrease Using the fan DX100R DX100S Only Operate the fan using the on off switch not supplied Repeat to switch off DX100TR DX100TS Only O...

Page 11: ...e for the adjustable time delay then goes into automatic mode Pull Cord operation Use the integral pull cord switch When the fan is switched off the fan continues to operate for the adjustable time delay then goes into automatic mode DX100PIRR DX100PIRS Only The sensor detects movement in the room and activates the fan When movement is sensed the fan will run for a pre set over run period and any ...

Page 12: ...ernational below United Kingdom Xpelair have a comprehensive range of services including Free technical advice help desk from Engineers on all aspects of ventilation Free design service quotations and site surveys Service and maintenance contracts to suit all requirements Please ask for details By telephone on Techline 44 0 844 372 7766 By fax on Techfax 44 0 844 372 7767 At the address below Head...

Reviews: