DUCT FITTINGS:

This Hood Must Use an

6" Round Duct. It Can

Transition to 3-1/4" x

10" or 3-1/4" x 12" Duct.

Use  this  chart  to  compu-

te  maximum  permissible 

lengths  for  duct  runs  to 

outdoors.

NOTE:

 

Do not exceed maxi-

mum permissible equivalent 

lengths!

Maximum  duct  length: 

100  feet  for  range  ho-

ods.
Flexible ducting:

If  flexible  metal  ducting 

is used, all the equivalent 

feet  values  in  the  table 

should  be  doubled. The 

flexible metal duct should 

be  straight  and  smooth 

and extended as much as 

possible.
DO NOT use flexible plastic 

ducting.

NOTE:

 

Any home ventilation 

system, such as a ventilation 

hood,  may  interrupt  the 

proper flow of combustion 

air  and  exhaust  required 

by fireplaces, gas furnaces, 

gas water heaters and other 

naturally vented systems. To 

minimize the chance of in-

terruption of such naturally 

vented systems, follow the 

heating equipment manu-

facturer’s  guidelines  and 

safety  standards  such  as 

those published by NFPA.

Duct 

Piece:

Dimensions:

Equivalent 

Number 

Length*:

Quantity

Used:

Total

Equivalent

Length:

Round, straight 1 ft. (per foot 

lenhgth)

3-1/4" x 10" 

straight

1 ft. (per foot 

lenhgth)

90° elbow

12 ft.

45° elbow

7 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

14 ft.

10 ft.

3-1/4" x 10"

3-1/4" x 12"

45° elbow

8 ft.

6 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

33 ft.

24 ft.

6" round to 

rectangular

2 ft.

Rectangular to 

8" round

2 ft.

3-1/4" x 10"

3-1/4" x 12"

6" round to 

rectangular 

transition 90° 

elbow

4 ft.

4 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular to 

6" transition 

90° elbow

4 ft.

4 ft.

Round wall 

cap with 

dramper

24 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular 

wall cap with 

dramper

24 ft.

18 ft.

Round roof 

cap

33 ft.

*Actual  length  of  straight  duct  plus  duct 

fitting  equivalent.  Equivalent  length  of  duct 

pieces  reflect  requirements  for  good  venting 

performance with any ventilation hood.

Total Duct Run =

Summary of Contents for XOMI36G

Page 1: ...A Manual de utilización USA F E XOMI36G XOMI42G NEED HELP Call our ventilation experts toll free al 800 966 8300 AVEZ VOUS BESOIN D AIDE Contactez nos experts au numéro gratuit 800 966 8300 NECESITA AYUDA Póngase en contacto con nuestros expertos a través del número gratis 800 966 8300 ...

Page 2: ...iginal purchaser for products purchased for ordinary home use in North America Should you require service for your XO product call a product service specialist at 800 966 8300 Improper Installation Service trips to the home to teach you how to use the product Resetting circuit breakers Damage caused after delivery EXPECT MORE FROM XO When buying any XO appliance you can be confident you have purch...

Page 3: ...s and vapors CAUTION To avoid motor bearing damage and noisy and or unbalanced impellers keep drywall spray construction dust etc off power unit CAUTION Please read specification label on product for further information and requirements WARNING TO REDUCETHE RISK OF FIRE ELECTRIC SHOCK OR INJURYTO PERSONS OBSERVE THE FOLLOWING A Use this unit only in the manner intended by the manufacturer If you h...

Page 4: ...inguisher ONLY if 1 You know you have a Class ABC extinguisher and you already know how to operate it 2 The fire is small and contained in the area where it started 3 The fire department is being called 4 You can fight the fire with your back to an exit aBased on kitchen firesafety tips published by NFPA Proper maintenance of the Range Hood will assure proper performance of the unit INSTALLATION I...

Page 5: ...ps after a prolonged use of the appliance C No food must be cooked flambè underneath the hood D The use of an unprotected flame is dangerous for the filters and could cause fires E Watch constantly the fried food in order to avoid the cooking oil flares up F Before performing any mainteinance operation disconnect the hood from the electrical service The manufacturers will not to accept any respons...

Page 6: ...terruption of such naturally vented systems follow the heating equipment manu facturer s guidelines and safety standards such as those published by NFPA Duct Piece Dimensions Equivalent Number Length Quantity Used Total Equivalent Length Round straight 1 ft per foot lenhgth 3 1 4 x 10 straight 1 ft per foot lenhgth 90 elbow 12 ft 45 elbow 7 ft 3 1 4 x 10 3 1 4 x 12 90 elbow 14 ft 10 ft 3 1 4 x 10 ...

Page 7: ...pe or Duct Tape INSTALL THE DUCTWORK NOTE To reduce the risk of fire use only metal ductwork 1 Decide where the ductwork will run between the hood and the outside 2 A straight short duct run will allow the hood to perform most efficiently 3 Long duct runs elbows and transitions will reduce the performance of the hood Use as few of them as possible 4 Install a roof or wall cap Connect 6 round metal...

Page 8: ... 8 Hood Specifications Front of hood Side of hood Top of hood Mounting height and clearance Product dimensions and clearance XOMI36G XOMI42G ...

Page 9: ...e in 3 screws without completely tighte ning them Pay attention not to insert the screw into the hole marked with an X on the hole template the screws and expansion plugs must be suitable for the type of wall Take the upper part of the structure B Fig 3 and insert the 3 slots onto the 3 screws that are not completely tighte ned Rotate slightly to fit Fig 3 Drive in the fourth screw X and tighten t...

Page 10: ...Fig 6 Fix the flexible pipe to the prepared air evacuation hole Fig 7 Take the upper chimney piece and fix it to the structure using the 2 screws A Fig 8 Join the lower chimney piece with the upper one and fix it carefully using adhesive tape L Fig 9A Unscrew the 2 screws O max 3 mm Fig 9A Insert the exhaust unit inside Fig 5 Fig 6 Fig 4 ...

Page 11: ... 11 Fig 9 Fig 7 Fig 8 ...

Page 12: ... Drive in the 3 screws N supplied and tighten the 2 screws O Fig 9B Fix the air evacuation pipe H not supplied onto the connection flange F Fig 10 Remove adhesive tape L and rest the lower chimney piece above the cooker hood Fig 11 If the cooker hood is supplied with a lower chimney piece that must be fixed Fig 11 Fig 13 Fig 12 Fig 10 ...

Page 13: ...m the hood by acting on the relevant handles Fig 13 Then screw the lower chimney piece pipe to the inside of the hood using screws P Fig 12 Relocate the filters in their seat IMPORTANT Therangehoodmustbesecuredtowallstudsorusedrywallanchors capable of supporting 75 lbs ...

Page 14: ...rcuit and protected by a 15 or 20 amp circuit breaker or time delay fuse Wiring must be 2 wire with ground If the electrical supply does not meet the above requirements call a licensed electrician before proceeding Route house wiring as close to the installation location as possible in the ceiling or back wall Refer to Wiring Locations on page 15 Connect the hood wiring to the house wiring in acco...

Page 15: ...ons to power supply the electrical box must be secured in place as indicated in Fig 14 Before installing the appliance fix the electrical box as indicated in Fig 14 Fig 14B Remove the 3 fixed screws Fig 14A Lift the electrical plant box Fig 14C Position the electrical box so it is in the line with the holes of the previously removed screws and tighten ...

Page 16: ... cover 3 Secure the power supply conduit to the cover 4 Connect the wires of the hood to those of the power supply as described Fig 15B BLACK L line WHITE N neutral GREEN YELLOW G ground A double pole switch properly rated must be installed to provide the range hood power supply disconnection Connect the electrical conduit to the Field Wiring Compartment using listed conduit fittings Fig 15 ...

Page 17: ... at a mini mum height of 27 from an electric cooker stove or 32 from gas or combined cooker stoves Ifaconnectionductworkcomposed of two parts is used the upper part must be placed outside the lower part Do not connect the range hood exhaust duct air to the same duct air used to exhaust hot air or fumes from other appliances other than electrical Before proceeding with the assembly operations remov...

Page 18: ...may be nec essary to cut the deviator to fit the width of the chimney as shown in picture 3 2 A sharp blade or Hacksaw is recommended to trim the plastic Carbon filter kit XORFK01 The kit includes an air diverter A 1 screw B and 2 rect angular filters C Fig 2 To remove the two screws E to take down the lower chi meny F ...

Page 19: ...e Not Included on the flange of connection 3 Fig 6 Remove adhesive tape 2 and rest the lower chimney piece above the cooker hood 6 Round Flexible Metal Duct Pipe Not Included 6 Round Flexible Metal Duct Pipe Not Included Fig 3 TofixtheairdiverterAonthesupport s bracket using the screw B as it is shown in the figure Once that the air diverter A has been fixed it is necessary to connect the flexible...

Page 20: ...move the aluminum panels by pulling the lever 1 out and pushing downwards 2 Fig 8 The charcoal filters C must be fit ted in the ducting unit located inside the hood Fig 9 Put the aluminum panels back in place Fig 7 ...

Page 21: ...ff and the LED of key F remains switched on with a fixed light until the motor starts up again at the first speed after fifty minutes and keys F and C start to flash again for ten minutes and so on By pressing any key for the exclusion of the hood light the hood will return immediately to its normal functioning e g if key D is pressed the clean air function is deactivated and the motor moves to th...

Page 22: ... is released back into the room The filters are not washable or re usable and must be replaced at least once every four months The active carbon filter saturation level depends on the frequency with which the appliance is used the type of cooking performed and the regularity with which the anti grease filters are cleaned Clean the cooker hood frequently both inside and outside using a cloth which ...

Page 23: ...ce causing rust DO NOT allow salt solutions disinfectants bleaches or cleaning compounds to remain in contact with stainless steel for extended periods Many of these compounds contain chemicals with may be harmful Rinse with water after exposure and wipe dry with a clean cloth Painted surfaces should be cleaned with warm water and mild detergent only ...

Page 24: ...ssity it can be replaced only by spe cialized personnel Replacing halogen light bulbs To replace the halogen light bulbs B remove the glass panel C using a lever action on the relevant cracks Replace the bulbs with new ones of the same type Caution do not touch the light bulb with bare hands ...

Page 25: ... 25 XOMI36G XOMI42G ...

Page 26: ... 26 OPTIONS AND ACCESSORIES Model XORFK01 Ductless Recirculating Filter Kit Model XOEDCMI Duct Cover Extension This accessory is available for installation with ceiling heights above 9 ft to 10 ft ...

Page 27: ... Check installation hardware Locate the hardware package packed with the hood and check contents TYPE DESCRIPTION N A 1 8 x 6 16 12 B 3 16 x 5 16 9 Aluminum filters 2 piece decorative duct cover dimension shown for reference only ...

Page 28: ...ved for dishwasher safe cleaning StandardChimneyfitsceilingsupto9fttall optional chimney extension for ceilings up to 10 ft Mounting Height from cooking surface 27 32 Duct Options and Electrical Requirements 6 inch duct required Ductless Option for applications where no ducting in available AC 120v 60Hz 4 18amp Options Optionalductcoverextensionisavailableforceiling heights up to 10 ft tall Model ...

Reviews: