USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH) 

______________________________________________________________________________________________________________________ 

 

20150610 Tower-Rack 6K-10K ISOTX

 

 - 38 

TROUBLESHOOTING 

               

 

PROBLEM DESCRIPTION 

PROBABLE ROOT CAUSE  

SUGGESTED ACTION 

* LCD does not show input voltage value 
* AC input failure alarm active  
(1 beep / 4s) however AC input source is OK 

Input power cord is not connected 

Check input power cord connection. 

Input power cord is connected into UPS 
outlet. 

Check input power cord connection. 

UPS cannot be powered on even AC input is OK. 
Beep alarm is active (1 beep/s) & LCD shows: 
 
 
   

EPO function is active. 
 

Re-establish emergency power off 
switch and set UPS in normal mode. 

UPS cannot be powered on even AC input is OK. 

ON  push  button  is  not  been  selected 
properly 

Push ON button during 2 seconds or 
longer 

1 beep / s alarm is active and LCD shows: 
   

Internal or external batteries are not 
properly connected 

Check battery connection. 

* Code 

27

 

*  Active:  
* Continuous beep 

Very high voltage at batteries or charger 
failure 

Batteries and charger must be 
inspected by qualified personnel 

* Code 

28

 

*  Active:  

* Continuous beep 

Very low voltage at batteries or charger 
failure 

Batteries and charger must be 
inspected by qualified personnel 

* Intermittent: 

 +

 

* 2 beeps per second. 

UPS overloaded  

Disconnect devices from UPS outlets 
until solving overload 

* Intermittent: 

 +

 

* 2 beeps per second. 
* By-Pass activated 

UPS overloaded. UPS has changed to 
BYPASS mode to avoid internal 
damage. 

Disconnect devices from UPS outlets 
until solving overload 

After repetitive small overloads, UPS 
has changed to BYPASS mode. 

Disconnect devices from UPS until 
solving overload. Then power off UPS 
and re-star it.

* Code 

43

 

* Active: 
* Continuous beep 

UPS has been automatically powered 
off because overload. 

Disconnect devices from UPS outlets 
until solving overload. Then power 
ON.

* Active:  
* Continuous beep 

UPS has been automatically powered 
off because short circuit detected at 
output. 

Check short circuit problem in 
devices connected to UPS 

 
* Intermittent:                 + 

EP

 

* 1 beep / s 

Parallel communication lost. 

Check parallel cables and PAR 00X 
text on each LCD. If problem is solved 
reset alarm with UP and DOWN 
simultaneous key selection. 

* Any of the error codes activated 

Probable internal UPS failure. 

Contact service center. 

Summary of Contents for Optima 6K

Page 1: ...ENGLISH VER 150610 TOWER AND RACK UPS USER MANUAL DOUBLE CONVERSION UPS...

Page 2: ...roperty of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without f...

Page 3: ...LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START U...

Page 4: ...There are dangerous voltages in DC Direct Current Capacitors Please Check Capacitor location in Figure 8 4 1 Wait at least 10 minutes after turning off UPS before opening it to access inside DANGER P...

Page 5: ...quency Magnetic Field IEC EN 61000 4 8 Level 4 EMS Low Freq Signals IEC EN 61000 2 2 EMS ESD IEC EN 61000 4 2 Level 4 EMS RS IEC EN 61000 4 3 Level 3 EMS EFT IEC EN 61000 4 4 Level 4 EMS SURGE IEC EN...

Page 6: ...S 6KEX 10KEX ISOTX for RACK UPS is an optional external module can be connected at any moment to the UPS Model Internal Batteries Ext Batt Connector Isolation Transformer 6KEX 10KEX Y Y No 6KEX 10KEX...

Page 7: ...ypass Switch Interruptor Bypass 3 EPO Emergency Stop Parada Emergencia 10 AC Input Breaker Breaker Entrada AC 4 Share Current for parallel UPS para UPS paralelas 11 FAN ISOTX Ventilaci n para ISOTX 5...

Page 8: ...tor Bypass 3 EPO Emergency Stop Parada Emergencia 10 AC Input Breaker Breaker Entrada AC 4 Share Current for parallel UPS para UPS paralelas 11 FAN ISOTX Ventilaci n para ISOTX 5 Parallel Port for par...

Page 9: ...RS 232 2 USB 3 EPO Emergency Power Off 4 Share Current Port for parallel function 5 Parallel Port for parallel function 6 SNMP Intelligent Slot 7 Cooling Fans 8 External Bypass Switch port MBS port 1...

Page 10: ...technical requirements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must...

Page 11: ...ver rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS th...

Page 12: ...ded with rack cabinets If not UPS distributor can provide original telescopic guides as optional accessory Small black handles included with the UPS are only for locking purposes UPS cannot be support...

Page 13: ...tilation and it will allow service UPS when required Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation ELECTRICAL REQUIREMENTS MANDATORY All Power lines mus...

Page 14: ...ring min size 8 AWG 10 mm2 ISOTX UNIQUE OUTPUT 1 x 120Vac 100 Watts SEPARE OUTPUTS 2 x 120Vac 50 Watts C U 6KVA con ISOTX Output 110 220V Unique Output Capacity 6000VA 4800W Output Voltage 120Vac AC B...

Page 15: ...Tower Rack 6K 10K ISOTX 15 LEAK CURRENT PROTECTION In many countries now a day it is legally required to install protections against current leakage to protect human beings in cases of leaks o dischar...

Page 16: ...plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected by breaker protected line to electric panel board UPS Input and Output...

Page 17: ...____________________________________ 20150610 Tower Rack 6K 10K ISOTX 17 ISOTX UPS MODEL CAN BE CONFIGURED IN 3 DIFFERENT MANNERS 1 TWO separate 110Vac isolated outputs Each 50 of total UPS capacity 2...

Page 18: ...__________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 18 RACK TYPE UPS 6 10K Optional ISOTX Module for RACK UPS 6 10K ISOTX module is optional accessory rack module UPS A...

Page 19: ...ION PROCEDURE UPS Tower type 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT connect UPS with...

Page 20: ...s kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires to proper pl...

Page 21: ...PS 6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 21 MODEL 6K 10KEX PARALLEL UPS...

Page 22: ...6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 22 MODEL 6K 10K ISOTX PARALLEL U...

Page 23: ...IMA UPS 6K 10K ENGLISH ______________________________________________________________________________________________________________________ 20150610 Tower Rack 6K 10K ISOTX 23 PARALLEL UPS CONTROL W...

Page 24: ...RE 1 Make sure all equipments connected to UPS are off 2 Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If...

Page 25: ...by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down when circuit opens 5 Check Maintenance Bypass Switch MBS located in UPS rear panel is...

Page 26: ...f LCD 12 All UPS will go to NORMAL Online mode at same time 13 Before setting to ON all external output breakers please revise AC voltage output on each UPS Please measure AC output voltage using a di...

Page 27: ...ks as ESCAPE key when LCD is in configuration menu mode TEST UP BATTERY TEST By selecting TEST key UPS enters into battery test mode during 10s UP It Works as UP key when LCD is in configuration menu...

Page 28: ...alarms error icons 2 ELAPSED TIMER When UPS switches to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code...

Page 29: ...with AC Line directly If under this mode UPS detects AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter starts working drai...

Page 30: ...d by inverter FREQUENCY CONVERTER FUNCTION CF CF function enable to generate output frequency as selected IMPORTANT NOTE When CF is activated bypass mode is automatically disable and maximum power out...

Page 31: ...have their own external protections to allow total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements...

Page 32: ...isable 6 Voltage Range for ECO mode 7 Frequency Range ECO mode 8 BYPASS mode 9 Battery Backup Security Time 10 Programmable Output note 1 11 Programmable Output Settings note 1 11 NO Battery startup f...

Page 33: ...Automatic Under this mode output frequency is selected according to input frequency 50Hz if input is 46Hz y 54Hz and 60Hz if input is 56Hz y 64Hz ATO mode is factory default value Parameter 3 Frequenc...

Page 34: ...before trying to enable it If ECO mode is disable next programs 06 and 07 don t need to be configured 06 ECO MODE Input Voltage Range LCD Parameter 2 Sets acceptable low voltage limit Parameter 3 Set...

Page 35: ...tputs OFF ATO This option allows programmable outputs to turn off when timer value is reached or very low voltage level whatever occurs first 11 PROGRAMMABLE OUTPUTS CONFIGURATION LCD Parameter 2 001...

Page 36: ...IS FACTORY SET VALUE 14 BATTERY CHARGER ADJUSTMENT LCD Parameter 2 Select Add or Sub for adjusting battery charger voltage Add or Reduce Parameter 3 available adjustment value is from 0V a 9 9V Factor...

Page 37: ...it 24 Inverter Relay Short Circuit 28 Battery connection problem BATT FAULT 35 Parallel Communication problem 36 UPS Output Short Circuit 41 HIGH Temperature 42 CPU communication problem 43 UPS Output...

Page 38: ...re Batteries and charger must be inspected by qualified personnel Code 28 Active Continuous beep Very low voltage at batteries or charger failure Batteries and charger must be inspected by qualified p...

Page 39: ...te Ext Charging Amps Corriente de Carga Charging Voltage Voltaje Cargador 2 0 A Max 273 0 VDC 96 92 EX ISO 90 86 EX ISO 88 84 EX ISO Depending on external battery configuration depende de cantidad de...

Page 40: ...ador de aislamiento con salida dual 2 x 110Vac Rack 6K 10K UPS Battery 3rd optional cab for ISOTX Rack 6K 10K UPS Bater as 3er por opci n Transf ISO opcional Specifications may change without further...

Page 41: ...ndling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out of warranty a reparation proposal will be sent to t...

Reviews: