USER MANUAL - OPTIMA UPS 6K/ 10K (ENGLISH)
______________________________________________________________________________________________________________________
20150610 Tower-Rack 6K-10K ISOTX
- 34
•
03: BYPASS Input Voltage Range
LCD
Parameter 2:
It adjusts low acceptable input voltage in bypass mode between
110V to 209V
Parameter 3:
It adjusts high acceptable input voltage in bypass mode between
231V - 276V.
04: BYPASS Input Frequency Range
LCD
Parameter 2:
It adjusts low acceptable input frequency in bypass mode.
In 50 Hz systems: from 46.0Hz to 49.0Hz.
In 60 Hz systems: from 56.0Hz a 59.0Hz.
Parameter 3:
It adjusts high acceptable input frequency in bypass mode.
In 50 Hz systems: from 51.0Hz to 54.0Hz.
In 60 Hz systems: from 54.0Hz a 64.0Hz.
05: ECO MODE
LCD
Parameter 3:
Enable or Disable ECO Mode
DIS:
Disable ECO mode
ENA:
Enable ECO mode
** We recommend to know very well how this function works before trying
to enable it.
If ECO mode is disable, next programs 06 and 07 don’t need to be configured.
06: ECO MODE Input Voltage Range
LCD
Parameter 2:
Sets acceptable low voltage limit.
Parameter 3:
Sets acceptable low voltage limit.
.
•
07: ECO MODE Frequency Input Range
LCD
Parameter 2:
It sets low frequency acceptable value in ECO mode
For 50 Hz system: 46.0Hz - 48.0Hz.
For 60 Hz system: 56.0Hz - 58.0Hz.
Parameter 3:
It sets high frequency acceptable value in ECO mode
For 50 Hz system: 46.0Hz - 48.0Hz.
For 60 Hz system: 56.0Hz - 58.0Hz.
08: BYPASS MODE SETTINGS
LCD
Parameter 2:
OPN
: Bypass ALLOWED. It allows Bypass mode according to Parameter 3
configuration
FBD
: Bypass NOT ALLOWED. Under this mode Bypass mode is prohibited and
UPS never will go to bypass mode no matter the situation.
Parameter 3:
ENA
: Bypass enabled. Enables BYPASS mode when necessary (manual by LCD
or automatic).
DIS
: Bypass disabled. It disables manual bypass mode selection by LCD panel.
When OFF push button is selected UPS turn OFF. Only automatic bypass mode
can be performed when internal failure or overload is detected by the UPS.