III - LIST OF PARAMÈTERS
02/99
13
A - DELAYS
Set Overspeed :
Overspeed delay.
GEN OverVolts :
Alternator overvoltage delay
GEN UnderVolts :
Alternator undervoltage delay
GEN OverFreq :
Alternator over frequency delay
GEN UnderFreq :
Alternator under frequency delay
G 2x OvCurr :
Delay assigned to the genset before overload triggering
G Revrse kW :
Delay assigned to the genset before triggering on an active reverse power
G Rvrs kVAr :
Delay assigned to the genset before triggering orse power
G Over % THD :
Delay assigned to the genset before triggering caused by a harmonic distortion rate higher than the set point.
SyncTimeout :
Delay assigned to the genset to synchronise on the mains or bus.
Sync Dwell Time :
Delay assigned to the parallel device to observe synchronisation, voltage equality, frequency equality and phase
shift.
kw Surge Enable :
Not used.
Test Delay :
Time the genset runs in test mode.
V4 Volts Status :
Delay to observe bus or voltage stability depending on the voltage configuration on V4.
Standby On :
Delay after mains failure before the genset starts in automatic mode with (control INS = 1).
Stanby Off :
Delay after mains return before load is removed from genset, in automatic mode with (control INS = 1).
Eng Preglow :
Delay for preheating of air intake glow plug(s) before start-up.
Engine crank :
Time for starter to trigger (period of one attempt).
CrankFail Rest :
Time between two start-up attempts.
Set Stabil Max :
Maximum delay assigned to the genset from starter throw-out to complete stabilisation in speed and voltage.
GE stabil min :
Minimum delay assigned to the genset from starter throw-out to closing of genset power delivery.
Coolin Down :
Engine cooling delay after genset is delivering power.
The equipment has been configured for a specific application. It is forbidden to modify the system
configuration without written consent of a person authorised by our company.
In the event of not respecting this procedure, our company disclaims all responsibility on the conse-
quences that could result from such action.
Http://www.xinke-hk.com
ShenZhen XinKe power equipment Co .Ltd