XP3-BD User Manual 

Page 25 of 30 

MANUL008R2V1 

 

 
 
 
 

 
 

           

This BD board does not   use     I/O units, the converted data will be sent directly into the PLC  

        

register. The channel’s corresponding PLC register ID is:  

 

Channel 

0CH 

1CH 

2CH 

3CH 

AD signal/Temperature 
value 

ID1000 

ID1001 

ID1002 

ID1003 

PID output value 

ID1004 

ID1005 

ID1006 

ID1007 

Set the target value 

QD1001 

QD1002 

QD1003 

QD1004 

D/A Output Value 

QD1000 

Kp 

QD1005 

QD1009 

Ki 

QD1006 

QD1010 

Kd 

QD1007 

QD1011 

Diff 

QD1008 

QD1012 

Dead Band 

-- 

QD1013 

Start/Stop 

Y1000 

Y1001 

Y1002 

Y1003 

 

 

Note:  
1.

  Both 0CH and 1CH are PT input channels; 2CH and 3CH are AD input channels  

2.  Kp:

 proportion parameter 

3.  Ki:

 Integral parameter 

4.  Kd:

 Differential parameter 

5.  Diff:

 Control   band      

Control   band     

     6.  (Diff):

 Carry on PID control in the assigned band;  

       7.  Start Signal

 (Y): Close PID control when Y is 0, open PID control when Y is 1   

       8.  Dead Band (Dead Band):

 Compare the current PID output value with the preceding PID  

       output value. If their difference is less than the set Dead Band, the module will not use the  
       current  
       PID output value and will transfer the preceding PID output. 

 

 
 
 
 
 

 
 
 

 
 
 

 

 

4-4 Assignment of input ID 

Summary of Contents for XP3-BD series

Page 1: ......

Page 2: ...0 2 7 Application of PID output value 10 2 8 Programs 11 Chapter 3 K type thermo coupling temperature PID board XP3 2TC P 3D 3 1 General 13 3 2 Specs 14 3 3 External installations and connections 15 3...

Page 3: ...ly on the main unit 2 Then connect the model online via XCP edit tool in the Window menu choose Config BD Board C Image 1 3 Click it in the Config BD Board C dialog box choose Other BD Just as shown i...

Page 4: ...UL008R2V1 2 AI and temperature sampling board XP3 2AD2PT BD 2 2 Specs 2 3 External installations and connections 2 1 General 2 5 Working Mode settings 2 6 Control settings 2 4 Assignment of input ID 2...

Page 5: ...5 of 30 MANUL008R2V1 2 1 General 14 bits high precision analogue input 2 Channel voltage 0 10V 0 5V selectable analogue input 2 channels PT temperature testing resistor PT100 two wire format temperatu...

Page 6: ...0 to 350 degrees C Resolution 0 15mV 10 16383 0 1 Digital Output band 0 to 16383 1000 to 3500 Integrate Precision 0 8 of full scale Convert Time 15ms 4 channels PID Output Value 0 to K4095 Vacant Defa...

Page 7: ...tallation of Board Open the board s cover at the back of XP3 As shown in the following image install it according to the pin arrangement Then fix it with screws close the cover 2 Connection See the fo...

Page 8: ...rameter 4 Kd Differential parameter 5 Diff Control proportion band 6 Control coil s status Y1000 Y1001 0 means stop PID control 1 means run PID control Description 0CH and 1CH are AD input channels 2C...

Page 9: ...decrease system s shake 5 Temperature control proportion band means in the assigned band carry on PID control beyond the band do not carry on PID control CH1 CH 0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 B...

Page 10: ...and Means in the assigned band to carry out PID control PID Temperature Control Curve is Shown Below Note Each parameter s reference value Kp 20 100 Ki 5 20 Kd 200 500 DIFF 100 200 This reference valu...

Page 11: ...800 QD1000 MOV ID1000 D10 M8000 END MOV K30 QD1004 MOV K5 QD1005 MOV K500 QD1006 MOV K150 QD1007 MOV K200 QD1008 MOV ID1004 D1000 Y1000 M8 2 8 Programs Write CH0 s input value into D10 Set CH0 s value...

Page 12: ...000 T200 K200 T200 T200 D1200 Y3 Y1000 M10 END MOV K30 QD1009 MOV K5 QD1010 MOV K500 QD1011 MOV K150 QD1012 D1100 K0 T200 is 10ms timer Convert PID output value 0 4095 to be value of 0 200 Via ON OFF...

Page 13: ...cs 3 3 External installations and connections 3 4 Assign input output ID 3 5 Working Mode settings 3 6 Control speciality 3 7 Programs 3 1 General Analogue input used by thermocouple K type temperatur...

Page 14: ...nts Temperature Testing Band 0 to 970 C Digital Output Band 0 9700 16 bits binary Output Points 2 points Output Format NPN collector open circuit transistor output Control Precision 0 4 C Resolution 0...

Page 15: ...tall Position of Expansion Board Installation Method of Expand Board 1 Open the expansion cover behind XP3 See the following diagram then install according to the pin and fix with screws 2 Connection...

Page 16: ...it and output transistor use optical coupling device to insulate Each public module is divided separately Response time The time from PLC drive optical coupling device to transistor ON OFF is not more...

Page 17: ...0CH ID1000 QD1000 QD1 001 QD1 002 QD1 003 QD1 004 Y1000 1CH ID1001 QD1005 QD1 006 QD1 007 QD1 008 QD1 009 Y1001 Note 1 Kp proportion parameter Ki integral parameter Kd differential parameter Diff cont...

Page 18: ...PID output value this period is called Temperature Control Cycle CH1 CH0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 0 2 Sec 0 2 Sec 1 20 Sec 1 20 Sec FD8306 H O O O O 0CH 1CH 3 5 Working Mode settings 1...

Page 19: ...control 2 Temperature Control Cycle When carrying out PID adjustment the output will carry on heating according to the duty cycle got by PID output value this period is called Temperature Control Cyc...

Page 20: ...MOV QD1000 K500 MOV QD1003 K5 MOV QD1002 K30 MOV QD1001 M8000 END K150 MOV QD1004 Y1000 M0 3 7 Programs Set value in CH0 as 800 80 degrees Set CH0 s Kp as 30 Start stop CH0 Set CH0 s Ki as 5 Set CH0...

Page 21: ...30 MANUL008R2V1 4 Analogue AI AO temperature sampling board XP3 2PT2ADIDA BD 4 1 General 4 2 Specs 4 3 External installations and connections 4 4 Assignment of input ID 4 5 Working Mode settings 4 6...

Page 22: ...R2V1 4 1 General 14 bits high precision analog input 10 bits high precision analog output 2 channels voltage 0 10V or 0 5V selectable analog input 2 channels PT temperature testing resistor PT100 2 wi...

Page 23: ...mA Temperature Testing band 100 to 350 C Distinguish Ratio 0 15mV 10 16383 0 1 C 1 1023 Digital Output band 0 to 16383 1000 to 3500 Integrate Precision 0 8 of the full scale Conversion Time 15ms 4 cha...

Page 24: ...raph and then install it according to the pin arrangement Then fix it with screws close the cover 2 Connection format As shown in the following graph Note Module s 0 20mA or 4 20mA output needs 24V po...

Page 25: ...1008 QD1012 Dead Band QD1013 Start Stop Y1000 Y1001 Y1002 Y1003 Note 1 Both 0CH and 1CH are PT input channels 2CH and 3CH are AD input channels 2 Kp proportion parameter 3 Ki Integral parameter 4 Kd D...

Page 26: ...14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4 filter 0 0 10V 1 0 5V 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4 filter 0 0 10V 1 0 5V 4 5 Working mode sett...

Page 27: ...l parameter Temperature control proportion band in the assigned band and will carry on PID control D A channel Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4...

Page 28: ...control 2 Temperature Control Cycle When carrying out PID adjustment the output will carry on heating according to the duty cycle got by PID output value this period is called Temperature Control Cyc...

Page 29: ...Programs Write channel 0 input temperature into D0 Write channel 1 output temperature into D2 Treat CH2 Pressure setting 0 10V as the set value in CH3 Write CH3 Pressure Feedback into D4 Set AD Channe...

Page 30: ...EMARK OF XINJE ELECTRICAL CO LTD REPLICATION OF THE INFORMATION CONTAINED WITHIN THIS DOCUMENT WITHOUT PRIOR NOTIFICATION AND AGREEMENT IS PROHIBITED Engineered and supplied by International partners...

Reviews: