2) Each channel’s working mode is assigned by the four bits of the corresponding register, each
bits definition is shown below:
Register FD8306:
1. Usage of four parameters: Proportion parameter (Kp), integral parameter (Ki), differential
parameter (Kd), control proportion band (Diff).
2.
Parameter P is proportion parameter, mainly reflect system’s wrap, when system wrap
appears, carry on control immediately to decrease the wrap.
3. Parameter I is integral parameter, mainly used to remove net difference, improve the systems
no-difference degree
4. Parameter D is differential parameter; mainly used to control the
signal’s change trend,
decrease system’s shake.
5. Temperature control proportion band means: in the assigned band, carry on PID control,
beyond the band, do not carry on PID control.
CH1
CH 0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
-
0
:
0~10V
1
:
0~5V
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
-
0
:
0/10V
1
:
0/5V
CH3
CH 2
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
-
-
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
-
-
2-5 Working Mode settings
1) Expansion’s input has voltage 0/5V and 0/10V. These
two modes and filter form to select. Set via special
FLASH data register FD8306 in PLC.
Refer to the graph (right) each register set the 4
channels’ modes, each register has 16 bits. From low bit
to high bit, each 4 bits set one channel mode.
FD8306 H O O O O
0CH
1CH
2CH
3CH