Word register PSW
Register
Function
Remark
PSW0
Start screen No.
PSW1
Current screen No.
PSW20
Screen width
( read only )
PSW21
Screen height
( read only )
PSW26
PSB amounts
( read only )
PSW27
PSW amounts
( read only )
PSW28
PFW amounts
Occupy PSW28
、
PSW29 ( read only )
PSW30
Year
( Hex) ( read only )
PSW31
Month
( Hex) ( read only )
PSW32
Day
( Hex) ( read only )
PSW33
Hour
( Hex) ( read only )
PSW34
Minute
( Hex) ( read only )
PSW35
Second
( Hex) ( read only )
PSW36
Week
( Hex) ( read only )
PSW40
Recipe index
PSW54
The device quantity
PSW60
COM1 communicate successful time
PSW61
COM1 communicate failure time
PSW62
COM1 communicate overtime time
PSW63
COM1 communicate data error time
PSW64
COM1 device version
PSW65
COM1 device type
PSW70
COM2 communicate successful time
PSW71
COM2 communicate failure time
PSW72
COM2 communicate overtime time
PSW73
COM2 communicate data error time
PSW74
COM2 device version
PSW75
COM2 device type
Word register PFW
Register
Function
Remark
PFW1
The screen No. after power on
PFW2
Background color setting
PFW10
Screen saver start time
PFW11
the screen number of screen saver
PFW20
COM1 baud rate
4800
、
9600
、
19200
、
38400
、
115200
、
187500
PFW21
COM1 data bit
7
、
8
PFW22
COM1 stop bit
0-1 bit, 1-1.5 bits, 2-2 bits
PFW23
COM1 CRC
0-None, 1-Odd, 2-Even
PFW24
COM1 station NO.
PFW25
COM2 send delay
Unit : ms
PFW30
COM2 baud rate
4800
、
9600
、
19200
、
38400
、
115200
、
187500
PFW31
COM2 data bit
7
、
8
PFW32
COM2 stop bit
0-1 bit, 1-1.5 bits, 2-2 bits
PFW33
COM2 CRC
0-None, 1-Odd, 2-Even
PFW34
COM2 station NO.
PFW35
COM2 send delay
Unit: ms
PFW60
Level 1 password
PFW60
、
PFW61
PFW62
Level 2 password
PFW62
、
PFW63
PFW64
Level 3 password
PFW64
、
PFW65
PFW66
Level 4 password
PFW66
、
PFW67