66
(2) Input signal setting
Parame
ter
Signal
Setting
Meaning
Range
P5-31
Zero clamp
/ZCLAMP
n.0000
(default)
Defaulted is not distribute to input
terminal
/Z-CLAMP
signal
is
distributed
to
input
terminal by parameter
P5-31,
Range:
0000-0014.
n.0002
Input signal from SI2 terminal
(3) Parameter setting
parameter
Meaning
Default
setting
Unit
Range
Change
Effective
P3-13
Zero clamp speed
10
rpm
0
~
300
Servo
OFF
At once
P3-12
Zero clamp mode
0
-
0
~
3
Servo
OFF
At once
P3-12 setting
Contents
0
ZCLAMP input signal is ON, forced speed command is 0, when the speed below
P3-13, switch to position mode and the servo lock in this position.
1
ZCLAMP input signal is ON, forced set the speed command to 0.
2
ZCLAMP input signal is ON, the speed below P3-13, switch to position mode and
the servo lock in the position.
Note: after entering zero clamp mode, present setting speed is higher than P3-13,
motor doesn’t run, the ZCLAMP signal must be OFF, then motor will run again.
3
ZCLAMP signal is ON, the setting speed is less than P3-13, switch to position
control mode, and servo is locked at this position. At this time, if setting speed is
over P3-13, the motor will run again.
5.6.7 Torque limit
1. Internal torque limit
Parameter
Meaning
Default
setting
Unit
Range
Modify
Effective
P3-28
Internal Forward
torque limit
300
%
0
~
300
Anytime
At once
P3-29
Internal reverse
torque limit
300
%
0
~
300
Anytime
At once
1. if this parameter value is less than external torque limit value, the final limit value is this parameter.
2. The unit is percent of the motor rated torque; the default value is 300%. The real max output torque
is limited by motor overload times.
2.
External torque limit (via input signal)
Parame
ter
Meaning
Default
setting
Unit
Range
Modify
Effective
P3-30
Forward external
torque limit
300
%
0
~
300
Anytime
At once
P3-31
Reverse external
torque limit
300
%
0
~
300
Anytime
At once
The unit is the percent of motor rated torque; the default value is 300%.