Xenteq ES Series User Manual Download Page 13

 

 

 

13

EN 

Remote control 

  If the remote control K01 is connected, it is important that the main 

switch  of  the  inverter  is  in  the ‘off’  position.  After  this,  the  inverter 
can be switched on and off by using the remote control. 

 

Fan cooling 

The  fan  is  both  temperature-  and  load  controlled.  So  the  rotation 
speed  of  the  fan  depends  on  the  internal  temperature  and  on  the 
load level. 
 

P R O T E C T I O N S

 

 

Low voltage protection 

When  the  input  voltage  drops  below  10.8  Volts  ±  0.2  Volts  (12 
Volts  system)  or  21.6  Volts  ±  0.4  Volt  (24  Volt  system),  a  buzzer 
will  sound 

twice

  every  8  seconds  and  the  red  ‘fault’  led  will  also 

flash 

twice

 
If  the  input  voltage  drops  even  further,  below  10.2  Volts  ±  0.2 
Volts (12 Volts system) or 20.4 Volts ± 0.4 Volts (24 Volts system), 
the  inverter  will  switch  off  the  230VAC  output  and  the  green 
‘inverter’ led will extinguish. While this protection is in operation, a 
buzzer  will  sound 

three  times

  every  8  seconds  and  the  red ‘fault’ 

led  will  also  flash 

three  times

.  When  the  input  voltage  has 

increased sufficiently, the inverter will restart automatically.  
 

Overvoltage protection 

If  the  input  voltage  rises  until  15.5  Volts  ±  0.2  Volts  (12  Volts 
system) or 31 Volts ± 0.4 Volts (24 Volts system), the inverter will 
switch  off  the  230VAC  output  and  the  green  ‘inverter’  led  will 
extinguish. While this protection is in operation, a buzzer will sound 

four  times

  every  8  seconds  and  the  red  ‘fault’  led  will  also  flash 

four times

. When the input voltage has decreased sufficiently, the 

inverter will restart automatically.  

 
Important 

The maximum input voltage that the inverter can tolerate is 15,5 
Volts  (12Vdc  system)  or  31Volts  (24  Vdc  system).  If  the  voltage 

Summary of Contents for ES Series

Page 1: ...ES series Gebruiksaanwijzing NL P a g i n a 2 Users manual EN P a g e 1 0 Gebrauchsanweisung DE S e i t e 1 8...

Page 2: ...7x het continu vermogen bedragen Controleer of opstartpieken binnen de capaciteits grenzen van de inverter vallen Als u meerdere apparatuur gelijk tijdig aan wilt gebruiken tel dan de vermogens bij e...

Page 3: ...ox zie pag 8 Gebruik bij voorkeur de meegeleverde kabelset De ES 300 bevat klemmen als aansluiting met de accu Wilt u dat deze inverter een vaste verbinding vormt met de accu dan adviseren wij om deze...

Page 4: ...n de eenheid met de aangesloten apparatuur werken dan is men verplicht om een isolatiebewaker te monteren Als er een ongeluk gebeurd omdat er geen isolatiebewaker aanwezig is heeft dit ernstige gevolg...

Page 5: ...tandsbediening aan en uit gezet worden Ventilator De ventilator is zowel temperatuur als belasting gestuurd De rotatie snelheid van de ventilator is dus afhankelijk van de interne temperatuur en van d...

Page 6: ...erter defect raken De reparatiekosten vallen dan niet onder de garantie Temperatuur beveiliging Als koeling van de ventilator onvoldoende is treedt de temperatuur beveiliging in werking De inverter sc...

Page 7: ...et een hogere capaciteit Inverter werkt geheel niet Geen ingang spanning aanwezig Controleer de verbindingen tussen accu en inverter Zekeringen defect Vervang de zekeringen alleen door gelijke waarden...

Page 8: ...e fault knippert continu Probleem op de uitgang van de inverter Er treedt een kortsluiting of overbelasting op Controleer de verbruikers Als het probleem verholpen is zal de inverter automatisch weer...

Page 9: ...gebruiksaanwijzing zijn wij genoodzaakt om de gemaakte kosten aan u door te berekenen In geval van een defect kunt u de inverter rechtstreeks opsturen of kiezen om de retour via uw dealer te laten ve...

Page 10: ...in the capacity limits of the inverter For the models from 600Watt a remote control is available as an optional see page 16 I N S T A LL A T IO N Mounting The inverter must be mounted in a space that...

Page 11: ...he heaver models two red and two black cables are included In this case always connect both cables on the and side If you wish to use your own cable set select the correct cable thickness correspondin...

Page 12: ...our ISO series For more info please visit our website www xenteq nl This standard applies to all mobile units with the exception of caravans campers boats and mobile selling vehicles I N U S E Operat...

Page 13: ...24 Volts system the inverter will switch off the 230VAC output and the green inverter led will extinguish While this protection is in operation a buzzer will sound three times every 8 seconds and the...

Page 14: ...30VAC output voltage if there is a short circuit of the output While this protection is activated the red fault led will flash continuously The inverter will restart automatically once the problem has...

Page 15: ...four times and the Fault led also flashes with the same frequency Problem with the inverter s input voltage See chapter protections Check the input voltage on the connection of the inverter Make sure...

Page 16: ...uld clean the exterior periodically with a damp cloth to prevent accumulation of dust and dirt Also check periodically all wires and connections Replace damaged wires immediately the ventilation vents...

Page 17: ...prepaid The ES inverters carry a one year warranty from selling date The warranty period is only valid when the copy purchase ticket is handed over with the repair The warranty only covers the costs o...

Page 18: ...innerhalb der Kapazit ts grenzen des Inverters liegen F r Modelle ab 600Watt ist optional eine Fernbedienung erh ltlich mit der der Inverter bedient werden kann siehe Seite 22 I N S T A LL A T IO N M...

Page 19: ...ku Wenn Sie w nschen dass dieser Inverter eine feste Verbindung mit dem Akku hat sollten Sie diese Klemmen beispielsweise durch Kabel sen ersetzen Bei den brigen Modellen erfolgt der Anschluss mit dem...

Page 20: ...en um sicher zu stellen das keine Personsgef hr lichen Situationen entstehen k nnen Sie finden mehr Information auf unser Website www xenteq nl G E B R A U C H Pr fen Sie vor Gebrauch ob die Kabel gut...

Page 21: ...10 2 Volt 0 2 Volt 12 Volt System oder 20 4 Volt 0 4 Volt 24 Volt System dann schaltet der Inverter den 230VAC Ausgang ab und das gr ne Inverter L mpchen erlischt Wenn diese Sicherung aktiv ist wird...

Page 22: ...erneut gestartet Kurzschluss am Ausgang Der Inverter schaltet die 230 V Ausgangsspannung ab wenn es am Ausgang zu einem Kurzschluss gekommen ist W hrend dieser Sicherung blinkt das rote Fehler L mpch...

Page 23: ...kt Tauschen Sie die Sicherungen aus nur durch gleiche Werte Zu d nne Kabel verwendet Es tritt ein zu hoher Span nungsverlust auf Bringen Sie Kabel an die zur L nge und zur Leistung passen L mpchen Feh...

Page 24: ...ei blinkt das L mpchen Fehler ebenso h ufig Temperatursicherung aktiv Kontrollieren Sie ob die L ftung funktioniert und oder ob der Inverter ausreichend L ftungsm glichkeiten hat Inverter steht an ein...

Page 25: ...R ckseite schicken Schicken Sie das Ger t immer frankiert ab F r die Wechselrichter der ES Serie gilt eine Garantie von ein Jahr ab Verkaufsdatum und nur f r die Reparaturzeit sowie f r Einzelteile in...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...Xenteq BV Banmolen 14 5768 ET Meijel Nederland Tel 31 0 77 4662067 Fax 31 0 77 4662845 info xenteq nl www xenteq nl V1D...

Reviews: