INSTALLATION MANUAL

Smart Charge Controller 1.1

    SCC-1

EN

Version:   1.0

Date:  16/02/2023

www.xemex.eu   

 

 

Installation Manual Smart Charge Controller 

Summary of Contents for SCC-1

Page 1: ...INSTALLATION MANUAL Smart Charge Controller 1 1 SCC 1 EN Version 1 0 Date 16 02 2023 www xemex eu Installation Manual Smart Charge Controller ...

Page 2: ...tion Please read the manual carefully to ensure that you are familiar with all its contents Follow the instructions in the manual carefully Always perform the actions in the correct order This manual should be kept in a safe dry and shady place for future reference If you lose this manual you can request a new copy from the supplier 1 1 Target group The installation and operation of this device an...

Page 3: ...Controller 5 Use current transformers CTs with built in TVS transient voltage suppressor with a dielectric strength of 3 5KV 50Hz 1min minimum and an operating voltage of 660V Do not use current output current transformers ratio such as 1 amp or 5 amp current transformers they may irreversibly damage the Smart Charge Controller 6 Ensure that current transformers are placed behind fuses or circuit ...

Page 4: ... consumption Capacity tariff 4 2 Overview of functionalities connection points 4 3 Conditions for the proper functioning of the energy management function The proper functioning of the energy management function of the Smart Charge Controller depends on the Dynamic Load Balancing functionality of the EV charging station It is assumed that this Dynamic Load Balancing functionality works as follows ...

Page 5: ...perature 20 C 80 C Operating humidity 10 95 RH non condensing Storage humidity 5 95 RH non condensing Pollution Degree 2 Altitude 2000m Application area Residential inside suitable meter cupboard 4 4 3 Power supply interface Connector Screw terminal connector for N L1 and functional earthing Voltage range 230 VAC 10 Frequency 50 Hz Power 5 W Overvoltage category II External fuse 16 A 4 4 4 Modbus ...

Page 6: ...sult in dangerous situa tions when working with electricity The electrical system must be completely disconnected from all power sources mains before carrying out any installation work www xemex eu Installation Manual Smart Charge Controller pg 09 1 2 3 4 11 12 13 14 230V AC N 230V AC L1 P1 kabel naar Slimme meter LAN kabel naar EV Oplader RS485 kabel naar EV Oplader B PE RS485 kabel naar EV Oplad...

Page 7: ...ion Manual Smart Charge Controller pg 10 This label is located on the side of the Smart Charge Controller PLEASE NOTE Do not interchange N terminal 2 with L terminal 3 The current direction import vs export is derived from the AC connection If the AC connection is reversed the device will not measure the current direction correctly PLEASE NOTE Do not reverse the polarity of the CT wires If the CT ...

Page 8: ...4 Commissioning The buttons and the LCD menu can be used to set the device to commissioning mode In commissioning mode the device will act as a Wi Fi access point 3 The name and password of the access point are displayed on the LCD The Wi Fi SSID is the character string SCC followed by the last 8 digits of the LDN of the device The Wi Fi code is a random 6 digit number generated when the device st...

Page 9: ...urrent Current transformers P1 CT ratio 7 5 2 Meter settings The Meter settings page contains the following parameters Meter to emulate drop down with supported meter types o Eastron SDM72D M with Modbbus prodotcol RTU o EMU Professional Modbus TCP If TCP is chosen for Modbus protocol the following must be entered o IP address o TCP port www xemex eu Installation Manual Smart Charge Controller pg ...

Page 10: ...Max charge current at commissioning 8 Use operation www xemex eu Installation Manual Smart Charge Controller pg 17 1 From the home screen press OK You are now in the charging mode SCC 1 HOME CHANGE mode ECO 2 The selected mode is displayed You can select the following modes ECO PV only ECO PV 6 A CAPACITY 4 kW CAPACITY 5 kW CAPACITY 6 kW CAPACITY 7 kW 22 kW SELECT MODE CAPACITY 4 kW SET ECO PV 6 A...

Page 11: ...re versions are displayed Press OK to return to the home screen Press or to navigate to a previous next menu screen www xemex eu Installation Manual Smart Charge Controller pg 19 8 4 Settings This screen displays a list of settings SCC 1 HOME CHANGE mode ECO 1 From the home screen press until you get to the Setting screen phases SETTINGS SCC 1 OK Number of 3 SETTINGS list settings Press OK to SCC ...

Page 12: ...rmware update If you press OK for less than 5 seconds you will return to the home screen To enable a firmware update the Smart Charge Controller must be connected to the home router via Wi Fi and have Internet access see 7 5 3 www xemex eu Installation Manual Smart Charge Controller pg 21 8 7 Restoring factory settings In this screen the device can be reset to the factory settings SCC 1 HOME CHANG...

Page 13: ...n LED does not flash When the current is not measured correctly Fault table 12 Environment Waste disposal Dispose of the product packaging materials in accordance with local laws and regulations DISPOSAL OF ELECTRICAL AND ELECTRONIC EQUIPMENT AEEA WEEE Electrical and electronic equipment WEEE contains materials components and substances which can be hazardous and present a risk to human health and...

Page 14: ...he conformity assessment procedure Modules B C the certificate of the EU type examination 212140635 AA 00 Where applicable Description of accessories and components including software enabling the radio equipment to function as intended and cov ered by the DoC All the products listed carry the CE mark Schoten Belgium 3 June 2022 14 Warranty For the duration and conditions of the warranty we advise...