ADVANCED SETTINGS - CALIBRATION
43
>>
Temperature Calibration Table
• Determine the temperature difference using an accurate thermometer, then use the
following table to adjust your thermostat calibration.
THERMOSTAT
FAHRENHEIT CELSIUS
CALIBRATION NUMBER
CHANGE
CHANGE
+3.0
+6°F
+3.0°C
+2.5
+5°F
+2.5°C
+2.0
+4°F
+2.0°C
+1.5
+3°F
+1.5°C
+1.0
+2°F
+1.0°C
+0.5
+1°F
+ .5°C
0.0
0°F
0°C
-0.5
-1°F
-.5°C
-1.0
-2°F
-1°C
-1.5
-3°F
-1.5°C
-2.0
-4 °F
-2.0°C
-2.5
-5°F
-2.5°C
-3.0
-6°F
-3.0°C
ADVANCED SETTINGS - CALIBRATION
42
>>
Calibration of Temperature or Relative Humidity
The TrueTouch™ Thermostat is rated for an accuracy of +/-1°F (+/-0.5°C) with temperature
and +/- 5% for Relative Humidity.
If you have determined due to drafts, sunlight or other environmental factors that your ther-
mostat requires calibration, follow this easy guide. Common cause of offset are lack of air
circulation, drafts or skylights in the direct vicinity of the thermostat.
Measure humidity with a conventional hygrometer or any other device that provides a
accurate reading. Then compare to the reading on your TrueTouch™ thermostat and
calibrate by up to +/- 15 degrees.