6
F06
Low-battery alarm OFF. When the state-of-charge
percentage has risen above this value and the alarm relay
is activated, the alarm relay will be deactivated again.
When
FULL
is selected the alarm relay is deactivated
when the charged parameters are met.
Default
Range
Step size
80.0%
0.0 – 100.0% /
FULL
1.0%
F07
Under-voltage alarm. When the battery voltage falls
below this value, after 10 seconds the message
Lo
will
appear on the display and the alarm relay will be
activated.
Default
Range
Step size
10.5 V
OFF / 8.0 – 33.0 V
0.1 V
F08
Over-voltage alarm. When the battery voltage rises above
this value, after 5 seconds the message
Hi
shall appear on
the display and the alarm relay will be activated.
Default
Range
Step size
16.0 V
OFF / 10.0 – 35.0 V
0.1 V
F09
Charge efficiency factor (CEF). It is recommended to
keep this value at
AU
(automatic calculation). The value
A90
resets the automatic calculation to 90%. A manual
setting is represented by
Uxx
where
xx
is the charge
efficiency. (See page 2 for more info about CEF.)
Default
Range
Step size
AU
U50 – U99 / AU /
A90
1%
F10
Peukert exponent (discharge efficiency). When unknown
it is recommended to keep this value at
1.25
. A value of
1.00
disables the Peukert compensation. Call Customer
Service or your battery manufacturer before changing
this setting.
Default
Range
Step size
1.25
1.00 – 1.50
0.01
Summary of Contents for Xantrex Battery Monitor
Page 2: ...Xantrex Battery Monitor Owner s Guide ...
Page 9: ...viii ...
Page 33: ...24 ...
Page 34: ...Monitor de baterías Xantrex Guía del usuario ...
Page 62: ...Xantrex Akku Monitor Benutzer Handbuch ...
Page 90: ...Controlleur de batterie Xantrex Manuel d entretien ...
Page 117: ...108 ...
Page 118: ...Sistema di monitoraggio batterie Xantrex Guida dell utente ...