
26
2.0 INSTALLATION
©2000 Xantrex Technology Inc.
Table 4
Minimum Recommended Wire Size (Input and Output)
Inverter Model
AC Input
AC Output
120 VAC
220-240 VAC
120 VAC
220-240 VAC
DR1512
#8 or 6 AWG
#10 AWG
#12 AWG
#16 AWG
DR2412
#6 AWG
#10 AWG
#10 AWG
#14 AWG
DR1524
#8 or 6 AWG
#10 AWG
#12 AWG
#16 AWG
DR2424
#8 AWG
#10 AWG
#10 AWG
#14 AWG
DR3624
#6 AWG
Not Available
#8 AWG
Not Available
975-0012-007
AC Wiring
Before wiring the input of the inverter, refer to the table below for the minimum recommended
wire size.
NOTE: Refer to the NEC for actual wire sizes for specific installations.
Summary of Contents for Trace DR Series
Page 1: ...Installation Operator s Manual DR Series Inverter Charger ...
Page 2: ......
Page 81: ......
Page 82: ......
Page 83: ......